<Indoor unit address>
6
Push the [menu] button until the CODE No. flashes. And using the [ or
] buttons,
specify the CODE No.13.
7
Push the [menu] button until the SET DATA flashes. And using the [ or
] buttons, set
an indoor unit address.
8
Push the [OFF timer] button to confirm the SET DATA.
<Group address>
9
Push the [menu] button until the CODE No. flashes. And using the [ or
] buttons,
specify the CODE No.14.
10
Push the [menu] button until the SET DATA flashes. And using the [ or
] buttons, set
a group address.
If the indoor unit is individual, set the address to 0000. (header unit : 0001, follower unit :
0002)
Individual
:0000
Header unit
:0001
Follower unit :0002
11
Push the [OFF timer] button to confirm the SET DATA.
12
When all the settings have been completed, push the [ON/OFF] button to return to normal
mode.
}