– 68 –
L01
DB01
C03
T101
IC801
J804
J805
J806
J807
Jumper wire
J804
J805
J806
J807
Item
19. Set temperature
correction
Operation flow and applicable data, etc.
Indoor Control P.C. Board (Factory Default)
In HEAT Operation
m
At shipment
¡
: With Jumper wire
×
: Cut Jumper wire
Jumper wire setup
J804
J805
×
×
×
¡
¡
×
¡
¡
HEAT
shift value
–2
+4
+2
0
Description
1. Purpose
When the difference between the set temp.
of the remote controller and the room temp.
is wide due to the installation condition, etc,
the set temp. is corrected.
(HEAT operation only)
2. Description
The set temp. received from the remote
controller is corrected.
The correct value from –2°C to +4°C is
changed by the jumper wire on P.C. board of
the indoor microcomputer.
The following settings are availiable by DIP switch setup.
20. Various setting on
outdoor unit
(Power save,
Cooling-only, etc.)
Function
Power save
setup
Setting position
Control contents
Turn the switch to ON, when using the power save function.
SW802
No.1
ON
ON
OFF
OFF
No.2
OFF
ON
ON
OFF
Current limit
11A
8.5A
Full
Full (Default)
When using the air conditioner as a cooling-only
conditioner, turn the switch to ON.
(If the heating mode is selected by rimote controll, outdoor
unit will remain stop. If mixed with indoor unit cooling and
heating, outdoor unit performs cooling operation.)
When using the air conditioner as a heating-only
conditioner, turn the switch to ON.
(If the cooling mode is selected by rimote controll, outdoor
unit will remain stop. If mixed with indoor unit cooling and
heating, outdoor unit performs heating operation.)
Caution:Set the switch before turning on the power supply.
Cooling-only
setup
Heating-only
setup
SW801
1
2
3
4
ON
OFF
Heating only setting
Cooling only setting
SW802
1
2
3
4
ON
OFF
Select current limit
Power save function