– 40 –
7-2. Operation Data
Outdoor Unit: RAS-3M26UAV-E
<Cooling>
Temperature condition
No. of
operating
units
Indoor unit
Standard
pressure
Heat exchanger
pipe temperature
Indoor fan
Outdoor fan
Compressor
revolution
(rps)
Indoor
Outdoor
A
B
C
P (MP)
T1 (ºC)
T2 (ºC)
27/19
35/-
1 unit
07
-
-
0.9 to 1.1
15 to 17
36 to 42
High
LOW
15.6
10
-
-
0.8 to 1.0
12 to 14
36 to 42
High
MED
23.3
13
-
-
0.7 to 0.9
10 to 12
36 to 44
High
MED
36.5
16
-
-
0.6 to 0.8
9 to 11
36 to 46
High
MED
50.3
18
-
-
0.6 to 0.8
10 to 12
36 to 47
High
High
52.1
22
-
-
0.6 to 0.8
8 to 10
36 to 47
High
High
52.7
24
-
-
0.6 to 0.8
8 to 10
36 to 47
High
High
70.0
2 units
07
07
-
0.8 to 1.0
10 to 12
47 to 49
High
MED
42.5
10
07
-
0.8 to 1.0
10 to 12
47 to 49
High
MED
42.5
13
07
-
0.8 to 1.0
10 to 12
47 to 49
High
MED
45.8
16
07
-
0.8 to 1.0
10 to 12
47 to 49
High
MED
49.1
18
07
-
0.8 to 1.0
10 to 12
47 to 49
High
High
52.3
22
07
-
0.8 to 1.0
10 to 12
49 to 51
High
High
55.6
24
07
-
0.7 to 0.9
9 to 11
51 to 53
High
High
58.9
10
10
-
0.8 to 1.0
10 to 12
47 to 49
High
MED
42.5
13
10
-
0.8 to 1.0
10 to 12
47 to 49
High
MED
49.1
16
10
-
0.8 to 1.0
10 to 12
49 to 51
High
High
52.3
18
10
-
0.8 to 1.0
10 to 12
49 to 51
High
High
55.6
22
10
-
0.7 to 0.9
9 to 11
51 to 53
High
High
58.9
24
10
-
0.7 to 0.9
9 to 11
51 to 53
High
High
62.2
13
13
-
0.8 to 1.0
10 to 12
47 to 49
High
High
55.6
16
13
-
0.7 to 0.9
9 to 11
51 to 53
High
High
58.9
18
13
-
0.7 to 0.9
9 to 11
51 to 53
High
High
62.2
22
13
-
0.7 to 0.9
9 to 11
51 to 53
High
High
62.2
24
13
-
0.7 to 0.9
9 to 11
51 to 53
High
High
62.2
16
16
-
0.7 to 0.9
9 to 11
52 to 54
High
High
62.2
18
16
-
0.7 to 0.9
9 to 11
52 to 54
High
High
62.2
22
16
-
0.7 to 0.9
9 to 11
52 to 54
High
High
62.2
24
16
-
0.7 to 0.9
9 to 11
52 to 54
High
High
62.2
18
18
-
0.7 to 0.9
9 to 11
52 to 54
High
High
62.2
22
18
-
0.7 to 0.9
9 to 11
52 to 54
High
High
62.2
24
18
-
0.7 to 0.9
9 to 11
52 to 54
High
High
62.2
3 units
07
07
07
0.8 to 1.0
11 to 13
51 to 53
High
High
59.8
10
07
07
0.8 to 1.0
11 to 13
51 to 53
High
High
59.8
13
07
07
0.8 to 1.0
11 to 13
51 to 53
High
High
59.8
16
07
07
0.8 to 1.0
11 to 13
51 to 53
High
High
59.8
18
07
07
0.8 to 1.0
11 to 13
51 to 53
High
High
59.8
22
07
07
0.8 to 1.0
11 to 13
51 to 53
High
High
59.8
24
07
07
0.8 to 1.0
11 to 13
51 to 53
High
High
59.8
10
10
07
0.8 to 1.0
11 to 13
51 to 53
High
High
59.8
13
10
07
0.8 to 1.0
11 to 13
51 to 53
High
High
59.8
16
10
07
0.8 to 1.0
11 to 13
51 to 53
High
High
59.8
18
10
07
0.8 to 1.0
11 to 13
51 to 53
High
High
59.8
22
10
07
0.8 to 1.0
11 to 13
51 to 53
High
High
59.8
24
10
07
0.8 to 1.0
11 to 13
51 to 53
High
High
59.8
13
13
07
0.8 to 1.0
11 to 13
51 to 53
High
High
59.8
16
13
07
0.8 to 1.0
11 to 13
51 to 53
High
High
59.8
18
13
07
0.8 to 1.0
11 to 13
51 to 53
High
High
59.8
22
13
07
0.8 to 1.0
11 to 13
51 to 53
High
High
59.8
24
13
07
0.8 to 1.0
11 to 13
51 to 53
High
High
59.8
16
16
07
0.8 to 1.0
11 to 13
51 to 53
High
High
59.8
NOTES:
1. Measure surface temperature of heat exchanger pipe around of heat exchanger path U bent. (Thermistor
thermometer)
2. Connecting piping condition : 5 meters × 3 units (5 m / each indoor unit)