– 112 –
(3) Check procedures
Table 11-8-1
No.
Procedure
Check points
Causes
1
Turn off the power supply breaker
and remove the P.C. board
assembly from electronic parts
base. Remove the connecting
cables from the terminal block.
Check whether or not the fuse
(F01) is blown.
Impulse voltage was applied or the
indoor fan motor short-circuited.
2
Remove the connector of the
motor and turn on the power
supply breaker. If OPERATION
indicator flashes (once per
second), it is not necessary to
check steps (1 to 3) in the right
next column.
Check power supply voltage :
1. Between No. 1 and No. 3 of
CN301 (AC 220–240V)
2. Between and of C03
(DC 310–340V)
3. Between of IC122 and output
side of IC122 (DC 15V)
4. Between 12V and GND
5. Between 5V and GND
1. The terminal block or the
crossover cable is connected
wrongly.
2. The capacitor (C01), line filter
(L01), resistor (R02), or the
diode (DB01) is defective.
3. IC101, IC122 and T101 are
defective.
4. IC101, IC121, IC122 and T101
are defective.
3
Push [START / STOP] button once
to start the unit. (Do not set the
mode to On-Timer operation.)
Check power supply voltage :
1. Between CN03 and CN501
(DC 15–60V)
IC501 and IC502 are defective.
4
Shorten the restart delay timer and
start unit.
Check whether or not all indicators
(OPERATION, TIMER, PURE) are
lit for 3 seconds and they return to
normal 3 seconds later.
The indicators are defective or the
housing assembly (CN261) is
defective.
5
Push [START / STOP] button once
to start the unit,
• Shorten the restart delay timer.
• Set the operation mode to
COOL.
• Set the fan speed level to AUTO.
• Set the preset temperature
much lower than the room
temperature. (The unit
(compressor) operates
continuously in the above
condition.)
1. Check whether or not the
compressor operates.
2. Check whether or not the
OPERATION indicator flashes.
1. The temperature of the indoor
heat exchanger is extremely
low.
2. The connection of the heat
exchanger sensor is loose. (The
connector is disconnected.)
(CN602)
3. The heat exchanger sensor and
the P.C. board are defective.
(Refer to Table 11-3-1.)
4. The main P.C. board is
defective.
6
If the above condition (No. 5) still
continues, start the unit in the
following condition.
• Set the operation mode to
HEAT.
• Set the preset temperature
much higher than room
temperature.
1. Check whether or not the
compressor operates.
2. Check whether or not the
OPERATION indicator flashes.
1. The temperature of the indoor
heat exchanger is extremely
high.
2. The connection of the heat
exchanger sensor short-
circuited. (CN602)
3. The heat exchanger sensor and
the P.C. board are defective.
(Refer to Table 11-3-1.)
4. The main P.C. board is
defective
7
Connect the motor connector to
the motor and turn on the power
supply.
Start the unit the following
condition.
• Set the fan speed level to HIGH.
(The unit (compressor) operates
continuously in the above
condition in No. 5.)
1. Check it is impossible to detect
the voltage (DC 15V) between 3
and 4 of the motor terminals.
2. The motor does not operate or
the fan motor does not rotate
with high speed. (But it is
possible to receive the signal
from the remote controller.)
3. The motor rotates but vibrates
strongly.
1. The indoor fan motor is
defective. (Protected operation
of P.C. board.)
2. The P.C. board is defective.
3. The connection of the motor
connector is loose.