High Wall, Heat Pump Type
Service Manual
68
Toshiba
Packed valve handling precautions
• Open the valve stem until it touches the stopper.
Once it is in contact with the stopper, refrain from
applying any more force than is necessary.
• Securely tighten the valve stem cap with torque in
the following table:
NOTE
Hexagon wrench is required.
9-4-6. Wiring Connection
1) Remove the valve cover, the electric parts
cover and the cord clamp from the outdoor unit.
2) Connect the connecting cable to the terminal
as identified by the matching numbers on the
terminal block of indoor and outdoor unit.
3) Insert the power cord and the connecting cable
fully into the terminal block and secure it tightly
with screws.
4) Use vinyl tape, etc. to insulate the cords which
are not going to be used. Locate them so that
they do not touch any electrical or metal parts.
5) Secure the power cord and the connecting
cable with the cord clamp.
6) Attach the electric parts cover and the valve
cover on the outdoor unit.
Stripping length of connecting cable
Gas side
(Dia. 12.7 mm)
33 to 42 N·m
(3.3 to 4.2 kgf·m)
Gas side
(Dia. 9.52 mm)
33 to 42 N·m
(3.3 to 4.2 kgf·m)
Liquid side
(Dia. 6.35 mm)
14 to 18 N·m
(1.4 to 1.8 kgf·m)
Service port
14 to 18 N·m
(1.4 to 1.8 kgf·m)
4 mm
Model
RAS-07PKVP-E
RAS-07PKVP-
ND
RAS-10PKVP-E
RAS-10PKVP-
ND
RAS-13PKVP-E
RAS-13PKVP-
ND
Power
source
220–240 V ~50 Hz
220–230 V ~60 Hz
Maximum
running
current
9.5 A
Installation
fuse rating
16 A breaker or fuse (all types can be used)
Power cord
H07RN-F or 60245IEC66 (1.5 mm
2
)
Connecting
cable
Wire type: H07RN-F or 60245IEC66 (1.0 mm
2
)
Model
RAS-16PKVP-E
RAS-16PKVP-ND
RAS-18PKVP-E
RAS-18PKVP-ND
Power
source
220–240 V ~50 Hz
220–230 V ~60 Hz
Maximum
running
current
9.5 A
Installation
fuse rating
16 A breaker or fuse
(all types can be used)
Power cord
H07RN-F or 60245IEC66 (1.5 mm
2
)
Connecting
cable
Wire type: H07RN-F or 60245IEC66
(1.0 mm
2
)
40
40
10
L N
10
1 2 3
1
3
2
L
N
10
10
50
50
Connecting
cable
Terminal block
Earth line
Earth line
Connecting
cable
Power cord
Power cord