6.4 TRPRTX0402 (4 AI, 2 AO)
Analog Input Range: Set in MW register as defined in 6.1 for each channel used.
Input Type
Input Range
MW Setting for Input Range Type
Voltage
0 to 10V
1
0 to 5V
6
Millivolt
0 to 50mV
5
0 to 100mV
4
mA
4 to 20mA
0
0 to 20mA
3
RTD
Alpha 1
7
Alpha 2
8
PT1000
9
Thermocouple
J
1
4
K
1
E
1
R
1
S
1
B
1
N
1
T
1
Analog Output Range: Set in MW register as defined in 6.1 for each channel used.
Output Type
Output Range
MW Setting for Output Range Type
Voltage
0 to 10V
2
0 to 5V
1
mA
4 to 20mA
5
0 to 20mA
6
USB HOST OPERATION
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: [email protected]