. A3-IPDU
control
IPDU controls inverter compressors by issuing commands relating to compressor
speeds, speed increases/decreases, and current release control values via the
interface P.C. board.
The main control functions of the IPDU P.C. board are described below.
1. Current release control
To prevent inverter input current from exceeding the specified value, output
frequency is controlled with AC input current as detected by T02 mounted on the
control P.C. board.
Current control values for various outdoor units are shown below.
2. Heat sink temperature detection control
1) This control function is aimed at protecting
IPM
from overheating via a thermistor
(TH sensor) mounted in the compressor drive module (Q201) of A3-IPDU.
2) When TH
about 75~
8
0
°C
*1
is detected, the fan operation mode is raised by
one step,
followed by a series of additional step-ups right up to the highest mode
at a rate of
one step/5 seconds.
3) After step 2), the normal fan mode is restored when TH falls to <
about 75~
8
0
°C
*1
.
4) When TH
97
°C, compressors are shut down.
5) Compressors are restarted 2 minutes and 30 seconds later, with an error count of
1 recorded. If this is repeated four times (error count reaches 4), the error is
confirmed as final. The error [P07] is displayed. (There will be no more restarts.)
* Possible causes of the confirmed error include a heat buildup in the outdoor unit, fan
abnormality, blockage of the cooling duct, and IPDU P.C. board fault.
* The TH temperature used in this control function is the highest registered by A3-
IPDU1, A3-IPDU2.
3. Overcurrent protection control
1) When the overcurrent protection circuit on an IPDU P.C. board detects an
abnormal current, the compressor is shut down.
2) The compressor is restarted 2 minutes and 30 seconds later, with an error count
of 1 recorded. If the compressor successfully operates for at least 10 minutes after
a restart, the error count is cleared.
3) If the error count reaches 8, the error is confirmed as final.
•
A3-IPDU1 and
2
are each
provided with a TH sensor.
4. High pressure SW control
1) When the high pressure SW of an inverter compressor is activated, the
compressor is shut down with an error count of 1 recorded.
2) The compressor is restarted 2 minutes 30 seconds later, and, if it successfully
operates for at least 10 minutes, the error count is cleared.
3) If the error count reaches 4, the error is confirmed as final. The
check code
“P04”
is
displayed.
• Connected to A3-IPDU, the
high-pressure SW is
normally closed.
Item
Description of operation, numerical data, and other information
Remarks
Zone C
Zone B
Zone A
Zone D
I
1
I
2
Current
Zone A:Compressors are operated normally.
Zone D:The current operating frequency is maintained.
Zone B:Operating frequency is lowered.
Zone C:The lowering of operating frequency is halted
to maintain the current frequency.
Outdoor unit HP capacity
I1
I2
22
23.7
23.2
20
21.6
21.1
18
19.5
19.0
16
17.5
17.0
14
15.2
14.7
12
12.7
12.2
10
10.5
10.0
8
10.0
9.5
−
74
−
*1 It changes depending on
the model and temperature
condition.
AMP Air Conditioning
www.ampair.co.uk | [email protected]
Содержание MAP1406HT8(J)P
Страница 304: ...For HT8 J P E HT8 J P TR model 303 AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 305: ...For T8 J P T7 J P T8P SG T8 J P ID T8 J P T model 304 AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 311: ... 310 For HT8 J P E HT8 J P TR model AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 312: ... 311 For T8 J P T7 J P T8P SG T8 J P ID T8 J P T model AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 318: ... 317 For HT8 J P E HT8 J P TR model AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 319: ... 318 For T8 J P T7 J P T8P SG T8 J P ID T8 J P T model AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 345: ...AMP Air Conditioning www ampair co uk sales ampair co uk ...