Check code
Location
of
detection
Description
System status
Error detection
condition(s)
Check items (locations)
Main
remote
controller
Outdoor 7-segment display
Check
code
Sub-code
P1
9
P1
9
Detected outdoor unit No.
I/F
4-way valve
reversing error
All stop
Abnormal refrigerating cycle
data is collected during
heating operation.
• Check for defect in main
body of 4-way valve.
• Check for coil defect in 4-
way valve and loose
connection of its
connector.
• Check resistance
characteristics of TS1
and TE1
,TE2
sensors.
• Check output voltage
characteristics of Pd and
Ps pressure sensors.
• Check for wiring error
involving TE1 and TL
1
sensors.
P
20
P
20
–
I/F
Activation of
high-pressure
protection
All stop
<During cooling operation>
Pd sensor detects pressure
equal to or greater than
3.85
MPa.
<During heating operation>
Pd sensor detects pressure
equal to or greater than
3.6 MPa.
• Check for defect in Pd
pressure sensor.
• Check service valves (gas
side, liquid side) to confirm
full opening.
• Check for defect in outdoor
fan.
• Check for defect in outdoor
fan motor.
• Check outdoor PMV
(PMV1,
3
, 4) for clogging.
• Check indoor/outdoor heat
exchangers for clogging.
• Check for short-circuiting
of outdoor suction/
discharge air flows.
• Check SV2 circuit for
clogging.
• Check for defect in outdoor
P.C. board (I/F).
• Check for defect in indoor
fan system (possible cause
of air flow reduction).
• Check opening status of
indoor PMV.
• Check indoor-outdoor
communication line for
wiring error.
• Check for faulty operation
of check valve in discharge
pipe convergent section.
• Check gas balancing SV4
valve circuit.
• Check SV5 valve circuit.
• Check for refrigerant
overcharging.
−
1
82
−
AMP Air Conditioning
www.ampair.co.uk | [email protected]
Содержание MAP1406HT8(J)P
Страница 304: ...For HT8 J P E HT8 J P TR model 303 AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 305: ...For T8 J P T7 J P T8P SG T8 J P ID T8 J P T model 304 AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 311: ... 310 For HT8 J P E HT8 J P TR model AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 312: ... 311 For T8 J P T7 J P T8P SG T8 J P ID T8 J P T model AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 318: ... 317 For HT8 J P E HT8 J P TR model AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 319: ... 318 For T8 J P T7 J P T8P SG T8 J P ID T8 J P T model AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 345: ...AMP Air Conditioning www ampair co uk sales ampair co uk ...