Check code
Location
of
detection
Description
System status
Error detection
condition(s)
Check items (locations)
Main
remote
controller
Outdoor 7-segment display
Check
code
Sub-code
P26
P26
01: Compressor 1 side
02: Compressor 2 side
IPDU
IPM
short-
circuit protection
error
All stop
Overcurrent is momentarily
detected during startup of
compressor.
• Check connector
connection and wiring on
A3-IPDU P.C. board.
• Check for defect in
compressor (layer short-
circuit).
• Check for defect in
outdoor P.C. board (A3-
IPDU).
P29
P29
01: Compressor 1 side
02: Compressor 2 side
IPDU
Compressor
position
detection circuit
error
All stop
Position detection is not
going on normally.
• Check wiring and
connector connection.
• Check for compressor
layer short-circuit.
• Check for defect in A3-
IPDU P.C. board.
–
P31
–
Indoor
unit
Other indoor
error
(group follower
unit error)
Stop of
corresponding
unit
There is error in other indoor
unit in group, resulting in
detection of E07/L07/L03/
L08.
• Check indoor P.C. board.
•
Check fan motor.
•
Check for defect in fan IPDU
P.C. board.
• Check fan motor.
• Check connection of fan
motor connector.
• Check for defect in fan IPDU
P.C. board.
•
Check fan motor.
•
Check for defect in fan IPDU
P.C. board.
• Check fan motor.
• Check connection of fan
motor connector.
• Check for defect in fan IPDU
P.C. board.
• Check fan motor.
• Check for defect in fan IPDU
•
•
Check power voltage of
the main power supply.
•
Check for defect in fan IPDU
•
Check connection of fan
IPDU P.C. board.
(Sub code: #0)
Fan IPDU over current
protection circuit
Flow of current equal to or
greater than the specified
value is detected during
startup of the fan.
(Sub code: #1)
Fan IPDU position
detection circuit Position
detection is not going on
normally.
(Sub code: #3)
Gusty wind, an obstruction,
or another external factor
Speed estimation is not
going on normally.
(Sub code: #4)
Fan IPDU over current
protection circuit
Flow of current equal to or
greater than the specified
value is detected during
operation of the fan.
(Sub code: #C)
Higher temperature than
the specified value is
detected during operation
of the fan.
(Sub code: #D)
The resistance value of
the sensor is infinite or
zero (open or short circuit).
(Sub code: #E)
Fan IPDU DC voltage
protection circuit
The DC voltage higher or
lower than the specified
value is detected.
All stop
All stop
All stop
All stop
All stop
All stop
All stop
IPDU
Outdoor fan
IPDU error
*Put in Fan
IPDU No. in [#]
mark
#0:Element short circuit
#1:Position detection circuit
error
#3:Motor lock error
#4:Motor current error
#C:
TH sensor
temperature error
#D:
TH sensor
short
circuit/release error
#E:Vdc voltage error
P22
P22
P.C. board.
Check for defect in fan
IPDU P.C. board.
P.C. board.
−
1
83
−
AMP Air Conditioning
www.ampair.co.uk | [email protected]
Содержание MAP1406HT8(J)P
Страница 304: ...For HT8 J P E HT8 J P TR model 303 AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 305: ...For T8 J P T7 J P T8P SG T8 J P ID T8 J P T model 304 AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 311: ... 310 For HT8 J P E HT8 J P TR model AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 312: ... 311 For T8 J P T7 J P T8P SG T8 J P ID T8 J P T model AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 318: ... 317 For HT8 J P E HT8 J P TR model AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 319: ... 318 For T8 J P T7 J P T8P SG T8 J P ID T8 J P T model AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 345: ...AMP Air Conditioning www ampair co uk sales ampair co uk ...