Outdoor Unit (18, 20, 22HP)
Model: MMY-MAP1806*, MAP2006*, MAP2206*
1.When compressor No.1 (front left) is faulty
:
Change the connection of wiring between Comp-IPDU and Fan-IPDU as shown in the below.
2.When compressor No.2 (front right) is faulty
:
Change the connection of wiring between Comp-IPDU and Fan-IPDU as shown in the below.
CN22
CN23
CN21
CN23
Change the connection of wiring which is connected to the CN21, 23 of Comp-IPDU1
・
Change to CN22 of Comp-IPDU2 from CN21 of Comp-IPDU1
・
Change to CN23 of Comp-IPDU2 from CN23 of Comp-IPDU1
(Tighten two wirings together with screw terminal)
Change the connection of wiring which is connected to the CN21, 23 of Comp-IPDU2
・
Change to CN22 of Comp-IPDU1 from CN21 of Comp-IPDU2
・
Change to CN23 of Comp-IPDU1 from CN23 of Comp-IPDU2
(Tighten two wirings together with screw terminal)
CN22
CN23
CN21
CN23
(
4
)
Turn on the power supply to all the units connected to the system.
This is the end of compressor backup operation setting.
−
2
40
−
AMP Air Conditioning
www.ampair.co.uk | [email protected]
Содержание MAP1406HT8(J)P
Страница 304: ...For HT8 J P E HT8 J P TR model 303 AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 305: ...For T8 J P T7 J P T8P SG T8 J P ID T8 J P T model 304 AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 311: ... 310 For HT8 J P E HT8 J P TR model AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 312: ... 311 For T8 J P T7 J P T8P SG T8 J P ID T8 J P T model AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 318: ... 317 For HT8 J P E HT8 J P TR model AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 319: ... 318 For T8 J P T7 J P T8P SG T8 J P ID T8 J P T model AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 345: ...AMP Air Conditioning www ampair co uk sales ampair co uk ...