Circuit
TK1
TK2
TK4
TK5
Connector
CN531 (Black)
CN532 (Green)
CN534 (Y
ellow)
CN535 (Red)
[H08]
Check code
Check code name
Oil level detective temperature
sensor error
Cause
TK1
, TK2, TK4, TK5
sensor
Open/Short
Sub-code:
01:
TK1 sensor error 02:
TK2 sensor error
04:
TK4 sensor error 05:
TK5 sensor error
The detected error is an oil level detective temperature sensor error
. Check disconnection of the wiring and resistance
value of the sensor
.
If the sensors are normal, replace the outdoor I/F P
.C. board.
[H15]
Ye
s
Ye
s
No
No
Cause
Check code
Check code name
Outdoor discharge temperature
sensor (TD2) misconnection
1. Coming-of
f
of TD2
sensor
2.
Misinstallation of
TD1
or
TD2 sensor,
miswiring,
characteristics error of resistance value
Is there no
miswiring or
misinstallation on
TD1/TD2
sensors?
Are resistance
characteristics of
TD2
sensor normal?
Correct miswiring/misinstallation.
TD1: CN502, white
TD2: CN503, pink
No
Ye
s
Is TD2
sensor
installed correctly?
Correct installation of sensor
.
Check I/F P
.C. board.
Sensor error
Replace the sensor
.
No
Ye
s
Ye
s
No error
No
Error
No
Ye
s
[H16]
Chec
k code
Cause
Chec
k code name
Oil le
v
el detection circuit error
TK1 temper
ature detectiv
e circuit
error (Sub-code:
01)
1.
Coming-off of
TK1 sensor
, mis
wir
ing,
char
acter
istics error of resistance v
alue
2.
Oil-equalization circuit error (Chec
k v
alv
e
,
capillar
y clogging, str
ainer clogging)
3.
Refr
iger
ant stagnation in the compressor shell
Is not
TK1 sensor
detached?
Is there
no mis
wir
ing or
misinstallation on
TD1/TD2/TK1/TK2/
TK4/TK5
sensors?
Are
char
acter
istics of
TK1 sensor resistance
v
alue nor
mal?
Correct installation of sensor
.
Sensor error
Replace clogging par
t.
Chec
k I/F P
.C
. board
Correct mis
wir
ing/misinstallation.
TD1:
CN502 white
TD2:
CN503 pink
TK1:
CN531, black
TK2:
CN532, green
TK4:
CN534, yellow
TK5:
CN535, red
Star
t a test oper
ation in COOL or HEA
T mode
.
Displa
y
TK1 sensor temper
ature on 7-segment displa
y with
SW01/02/03=[1] [12] [2].
Chec
k
TK1 sensor temp appro
x.
10 min
utes after compressor 1 has oper
ated.
If lo
w temper
ature contin
ues (appro
ximately outside temp) or temper
ature has
little change
, a clogging of str
ainer of oil-equalization circuit, clogging of
capillar
y tube
, or malfunction of chec
k v
alv
e is considered.
*See "Outdoor unit temper
ature sensor
characteristics" on "8-
10
.
Sensor Characteristics".
↓
↓
Comp
. 1
(in
ve
rter)
Str
ainer
Chec
k
va
lve
Capillar
y
tube
(TK1)
−
202
−
AMP Air Conditioning
www.ampair.co.uk | [email protected]
Содержание MAP1406HT8(J)P
Страница 304: ...For HT8 J P E HT8 J P TR model 303 AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 305: ...For T8 J P T7 J P T8P SG T8 J P ID T8 J P T model 304 AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 311: ... 310 For HT8 J P E HT8 J P TR model AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 312: ... 311 For T8 J P T7 J P T8P SG T8 J P ID T8 J P T model AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 318: ... 317 For HT8 J P E HT8 J P TR model AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 319: ... 318 For T8 J P T7 J P T8P SG T8 J P ID T8 J P T model AMP Air Conditioning www ampair co uk sales ampair co uk ...
Страница 345: ...AMP Air Conditioning www ampair co uk sales ampair co uk ...