51
Troubleshooting
Diagnostic procedure for check code
Check code
Operation cause
[8A]
1. Multi Controller PC board error.
Multi Controller PC board malfunction
Check lead connection between indoor unit and Multi Controller and outdoor unit.
If no error is detected, replace Multi Controller board (MCC-1210).
Check code
Operation cause
[97]
1. Connection error of (XY) for outdoor units.
Central management communication
2. Power source system error of the central
short circuit
controller and indoor unit.
3. Noise of peripheral devices.
4. Power failure.
5. Indoor PC board error, central controller error.
Are X,Y communication cables
normal?
Did power failure occur?
Clear the alarm after turning on
the power source, and start the
operation.
Check communication cable.
Indoor PC board error
j
j
h
No
Yes
Yes
Yes
Is the power source of either
central controller or indoor/
outdoor turned on?
Clear the alarm after turning on the
power source, and start the operation.
j
h
No
Yes
Is there a connection error of
power source wiring?
Check power source wiring.
j
h
Yes
No
j
No
Is the network address
different from main or sub
remote controller?
Eliminate noise interference.
h
No
Is [97] displayed only on
the central controller?
j
h
No
Yes
Is the operation status of
the indoor unit reflected on
the central controller?
Is there noise
interference, etc.?
Central controller error
h
h
Is there noise
interference, etc.?
h
No
No
Yes
No
Yes
Yes
j
j
i
i
Содержание HFC R407C
Страница 1: ...A90 0233 HFC R407C Super Multi System Service Manual Air Conditioner Multi Split Type System ...
Страница 2: ...2 ...
Страница 18: ...18 Wiring diagrams Outdoor unit MAR F105HTM8 PE ...
Страница 19: ...19 Wiring diagrams Outdoor unit ...
Страница 21: ...21 Refrigeration piping schematic diagram Outdoor unit ...
Страница 74: ...74 Exploded view and service parts Outdoor unit ...
Страница 75: ...75 Exploded view and service parts Outdoor unit 12 14 j ...
Страница 80: ...www toshiba aircon co uk MADE IN UK A90 0233 Revised October 2002 ...