40
Troubleshooting
Diagnostic procedure for check code
Is drain pump connected?
Does float switch operate?
Does drainage water collect?
Does drain pump operate?
Check for blockage of
drainage hose.
Is circuit wiring
normal?(*1)
(*1) For confirmation, check voltage under condition that
connector is connected to CN10, pins 5 and 7,
PJ10, pins 1 and 2
Is power to drain
pump turned on?(*2)
Drain pump error
Check connection of connector CN10
(Drain pump: Indoor main, PC board
(MCC-1292), CN10)
(Drain pump: Multi Controller, PC board
(MCC-1210) PJ10)
Check and modify wiring circuit.
(MCC-1292), (MCC-1210)
Indoor PC board error
(MCC-1292), (MCC-1210)
Float switch error
Check and modify wiring
circuit.
(*2) Check whether voltage of CN10/PJ10, pins
1 and 2/1 to 3 of the indoor main PC board,
is 230V or not (MCC-1292), (MCC-1210).
h
h
j
Yes
j
Yes
j
Yes
j
Yes
j
Yes
h
No
No
No
h
h
h
No
h
Check code
Operation cause
[0C]
Indoor sensor (TA) short or open circuit alarm
TA sensor open/short
TA sensor open/short has been detected. Check disconnection of connector connection (TA sensor: CN04)
circuit and resistance value characteristics of sensor.
When the sensors are normal, replace indoor PC board (MCC-1292).
Check code
Status of air conditioner
Operation cause
[0D]
Indoor unit fan stops.
TC sensor open/short
Indoor sensor (TC) short ‘Preheat defrost’ is
or open circuit alarm
displayed on R/C.
TC sensor open/short has been detected. Check disconnection of connection (TC sensor: CN05) circuit
and resistance value characteristics of sensor.
When the sensors are normal, replace indoor PC board (MCC-1292).
No
No
Check code
Status of air conditioner
Operation cause
[0b]
Operation stops for Multi
1. Float switch disconnection.
Drain pump fault
Controller fault.
2. Drain pump operation error.
Indoor unit or Multi
Indoor unit fan continues for 3. Drain hose blockage.
Controller
unit fault.
Содержание HFC R407C
Страница 1: ...A90 0233 HFC R407C Super Multi System Service Manual Air Conditioner Multi Split Type System ...
Страница 2: ...2 ...
Страница 18: ...18 Wiring diagrams Outdoor unit MAR F105HTM8 PE ...
Страница 19: ...19 Wiring diagrams Outdoor unit ...
Страница 21: ...21 Refrigeration piping schematic diagram Outdoor unit ...
Страница 74: ...74 Exploded view and service parts Outdoor unit ...
Страница 75: ...75 Exploded view and service parts Outdoor unit 12 14 j ...
Страница 80: ...www toshiba aircon co uk MADE IN UK A90 0233 Revised October 2002 ...