56
Troubleshooting
Diagnostic procedure for check code
Check code
Operation cause
[A7]
1. Outdoor unit service valve closed.
Suction temperature (TS) alarm (>40°C)
2. Blockage PMV assembly on the liquid line.
3. TS pressure switch error.
4. Insufficient refrigerant, blockage in pipe.
Are the gas pipe and liquid pipe
service valves of the outdoor unit
fully open ?
Is there a blockage in the
expansion valve on the liquid line?
Open valves fully.
Replace expansion valve.
j
j
h
h
No
Yes
Yes
No
Insufficient refrigerant, blockage,
pipe breakage.
Are the characteristics of TS
pressure switch normal?
(N/C type)
Replace TS pressure switch.
j
h
No
Yes
Check code
Operation cause
[AA]
High pressure sensor (Pd) short circuit
Pd sensor output voltage alarm
If there is an abnormal output voltage of Pd sensor: Check connector circuit (Pd sensor: PJ7) and output
voltage of the sensor.
If the sensor is normal, replace the outdoor interface PC board.
Sensor characteristics:
Input
12 V DC (± 10%) across red and black leads of the pressure sensor.
Output
0.5 to 4.5 V at 0 to 2.45 MPa across white and black leads of the pressure sensor.
Содержание HFC R407C
Страница 1: ...A90 0233 HFC R407C Super Multi System Service Manual Air Conditioner Multi Split Type System ...
Страница 2: ...2 ...
Страница 18: ...18 Wiring diagrams Outdoor unit MAR F105HTM8 PE ...
Страница 19: ...19 Wiring diagrams Outdoor unit ...
Страница 21: ...21 Refrigeration piping schematic diagram Outdoor unit ...
Страница 74: ...74 Exploded view and service parts Outdoor unit ...
Страница 75: ...75 Exploded view and service parts Outdoor unit 12 14 j ...
Страница 80: ...www toshiba aircon co uk MADE IN UK A90 0233 Revised October 2002 ...