Troubleshooting
Diagnostic procedure for check code
A
Does heating indoor fan
operate normally?
Are the Multi Controller PMV/
solenoid valves normal?
Is there any element to block
heat exchange in the room?
(1) Filter blockage
(2) Heat exchanger blockage
(3) Short circuit
Is communication line
between indoor and outdoor
units correct?
Refrigerant overcharge
Blockage
Pipe breakage
Abnormal overload
Yes
No
Yes
Yes
Eliminate blocking
element
Check and modify
wiring
No
Yes
Are the connector
connection and coil
normal?
Is there a blockage on
whole valve?
Check Multi Controller
PC board.
If defective, replace
Repair defective
position
No
Replace PMV unit
Yes
Yes
No
Are the
connection and fan
motor normal?
Repair defective
position
No
Yes
No
No
Is the sensor resistance
value characteristic TC
normal?
Replace TC sensor
No
Yes
Check indoor PC board.
If defective, replace
j
j
j
j
j
j
j
j
j
j
j
j
j
j
j
j
h
Содержание HFC R407C
Страница 1: ...A90 0233 HFC R407C Super Multi System Service Manual Air Conditioner Multi Split Type System ...
Страница 2: ...2 ...
Страница 18: ...18 Wiring diagrams Outdoor unit MAR F105HTM8 PE ...
Страница 19: ...19 Wiring diagrams Outdoor unit ...
Страница 21: ...21 Refrigeration piping schematic diagram Outdoor unit ...
Страница 74: ...74 Exploded view and service parts Outdoor unit ...
Страница 75: ...75 Exploded view and service parts Outdoor unit 12 14 j ...
Страница 80: ...www toshiba aircon co uk MADE IN UK A90 0233 Revised October 2002 ...