43
Troubleshooting
Diagnostic procedure for check code
Check code
Operation cause
[17]
1. Defective wiring of IPDU PC board.
Current detection circuit alarm
2. Defective IPDU PC board.
Refer to outdoor unit
Is wiring connector on IPDU PC
board normal?
Modify connection of wiring
Check IPDU PC board.
h
j
Yes
No
Check code
Operation cause
[1C]
1. Outdoor unit power source error.
Extension IC, EEPROM short circuit alarm
2. Interface PC board error.
(Outdoor unit error)
Is there an irregularity of outdoor
unit power source?
Check power source voltage.
Modify power source line.
Check noise interference from outside, etc.
Check interface PC board fault code.
h
j
Yes
No
Is compressor operation normal?
j
Yes
Compressor error
h
No