GX9 ASD Installation and Operation Manual
9
System Setup Requirements
•
When using the ASD as an integral part of a larger system, it is the responsibility of the ASD
installer/maintenance personnel to ensure that there is a fail-safe in place (i.e., an arrangement
designed to switch the system to a safe condition if there is a fault or failure).
•
Power factor improvement capacitors or surge absorbers
MUST NOT
be installed on the three-
phase output of the ASD.
•
Use of the built-in system protective features is highly recommended (i.e., Emergency Off,
Overload Protection, etc.).
•
The operating controls and system status indicators shall be clearly readable and positioned where
they may be viewed without obstruction.
•
Additional warnings and notifications shall be posted at the equipment installation location as
deemed required by
.
•
System safety features shall be employed and designed into the integrated system in a manner such
that system operation, even in the event of system failure, will not cause harm or result in system
damage or injury to personnel (i.e., Emergency Off, Auto-Restart settings, System Interlocks, etc.).
•
The programming setup and system configuration of the ASD may allow it to start the motor
unexpectedly. A familiarity with the
Auto-Restart
and
Retry
settings is a requirement to use this
product.
•
The setup procedures included within this manual may require a
Reset
before performing the
procedure. Application-specific settings may then be performed. The pre-Reset conditions may be
saved (see
•
There may be thermal or physical properties, or ancillary devices integrated into the overall system
that may allow for the ASD to start the motor without warning. Warning signs to this effect must be
clearly posted at or near the machinery/hazard.
•
If a secondary magnetic contactor (MC) or an ASD output disconnect is used between the ASD and
the load, it should be interlocked to halt the ASD before the secondary contact opens. If the output
contactor is used for bypass operation, it must be interlocked such that commercial power is never
applied to the ASD output terminals (U, V, or W).
•
When using an ASD output disconnect, the ASD and the motor must be stopped before the
disconnect is either opened or closed. Closing the output disconnect while the 3-phase output of the
ASD is active may result in equipment damage or injury to personnel.
CAUTION
Содержание GX9
Страница 1: ...GX9 ASD Install Op Manual TOSHIBA GX9 ASD INSTALLATION OPERATION MANUAL DN 66893 001 March 2014 ...
Страница 2: ......
Страница 3: ...Document Number 66893 001 March 2014 GX9 ASD Installation Operation Manual ...
Страница 4: ......
Страница 12: ...iv GX9 ASD Installation and Operation Manual ...
Страница 251: ...GX9 ASD Installation and Operation Manual 239 Figure 36 GX9 ASD 5 0 20 HP Enclosure ...
Страница 252: ...240 GX9 ASD Installation and Operation Manual Figure 37 GX9 ASD 25 75 HP Enclosure ...
Страница 253: ...GX9 ASD Installation and Operation Manual 241 Figure 38 GX9 ASD 100 200 HP Enclosure ...
Страница 254: ...242 GX9 ASD Installation and Operation Manual Figure 39 GX9 ASD 250 400 HP Enclosure ...
Страница 255: ...GX9 ASD Installation and Operation Manual 243 Figure 40 GX9 ASD 500 800 HP Enclosure ...
Страница 256: ...244 GX9 ASD Installation and Operation Manual Figure 41 GX9 ASD 900 1200 HP Enclosure ...
Страница 268: ......
Страница 269: ......