158
GX9 ASD Installation and Operation Manual
VI/II Input Gain
Program
Frequency
Speed Reference Setpoints
This parameter is used to fine tune the gain of the
VI/II
terminals.
Note:
See note on
VI/II
terminal.
This setting may be used to ensure that the 100% level of the input source (pot,
pressure transducer, flow meter, etc.) is also the 100% level setting of the ASD
system.
This is accomplished by setting the input source to 100% and adjusting this
setting to provide an output of 100% from the ASD.
Direct Access Number — F471
Parameter Type —
Numerical
Factory Default —
156
Changeable During Run —
Yes
Minimum — 0
Maximum — 255
RR Input Bias
Program
Frequency
Speed Reference Setpoints
This parameter is used to fine tune the bias of the
RR
terminal when this
terminal is used as the control input while operating in the
Speed Control
mode
or the
Torque Control
mode.
This setting may be used to ensure that the zero level of the input source (pot,
pressure transducer, flow meter, etc.) is also the zero level setting of the ASD
system.
This is accomplished by setting the input source to zero and adjusting this
setting to provide an output of zero from the ASD.
Direct Access Number — F472
Parameter Type —
Numerical
Factory Default —
100
Changeable During Run —
Yes
Minimum — 0
Maximum — 255
RR Input Gain
Program
Frequency
Speed Reference Setpoints
This parameter is used to fine tune the gain of the
RR
terminal when this
terminal is used as the control input while operating in the
Speed Control
mode
or the
Torque Control
mode.
This setting may be used to ensure that the 100% level of the input source (pot,
pressure transducer, flow meter, etc.) is also the 100% level setting of the ASD
system.
This is accomplished by setting the input source to 100% and adjusting this
setting to provide an output of 100% from the ASD.
Direct Access Number — F473
Parameter Type —
Numerical
Factory Default —
184
Changeable During Run —
Yes
Minimum — 0
Maximum — 255
RX Input Bias
Program
Frequency
Speed Reference Setpoints
This parameter is used to fine tune the bias of the
RX
input terminal when this
terminal is used as the control input while operating in the
Speed Control
mode
or the
Torque Control
mode.
This setting may be used to ensure that the zero level of the input source (pot,
pressure transducer, flow meter, etc.) is also the zero level setting of the ASD
system.
This is accomplished by setting the input source to zero and adjusting this
setting to provide an output of zero from the ASD.
Direct Access Number — F474
Parameter Type —
Numerical
Factory Default —
99
Changeable During Run —
Yes
Minimum — 0
Maximum — 255
Содержание GX9
Страница 1: ...GX9 ASD Install Op Manual TOSHIBA GX9 ASD INSTALLATION OPERATION MANUAL DN 66893 001 March 2014 ...
Страница 2: ......
Страница 3: ...Document Number 66893 001 March 2014 GX9 ASD Installation Operation Manual ...
Страница 4: ......
Страница 12: ...iv GX9 ASD Installation and Operation Manual ...
Страница 251: ...GX9 ASD Installation and Operation Manual 239 Figure 36 GX9 ASD 5 0 20 HP Enclosure ...
Страница 252: ...240 GX9 ASD Installation and Operation Manual Figure 37 GX9 ASD 25 75 HP Enclosure ...
Страница 253: ...GX9 ASD Installation and Operation Manual 241 Figure 38 GX9 ASD 100 200 HP Enclosure ...
Страница 254: ...242 GX9 ASD Installation and Operation Manual Figure 39 GX9 ASD 250 400 HP Enclosure ...
Страница 255: ...GX9 ASD Installation and Operation Manual 243 Figure 40 GX9 ASD 500 800 HP Enclosure ...
Страница 256: ...244 GX9 ASD Installation and Operation Manual Figure 41 GX9 ASD 900 1200 HP Enclosure ...
Страница 268: ......
Страница 269: ......