GX9 ASD Installation and Operation Manual
143
PID Feedback Delay Filter
Program
Feedback
Feedback Settings
This parameter determines the delay in the ASD output response to the motor
control feedback signal (signal source is selected at
Direct Access Number — F361
Parameter Type —
Numerical
Factory Default —
0
Changeable During Run —
Yes
Minimum — 0
Maximum — 255
PID Feedback Proportional Gain
Program
Feedback
Feedback Settings
This parameter determines the degree that the
Proportional
function affects the
output signal. The larger the value entered here, the quicker the ASD responds
to changes in feedback.
Direct Access Number — F362
Parameter Type —
Numerical
Factory Default —
0.10
Changeable During Run —
Yes
Minimum — 0.01
Maximum — 100.0
PID Feedback Integral Gain
Program
Feedback
Feedback Settings
This parameter determines the degree that the
Integral
function affects the
output signal. The smaller the value here, the more pronounced the effect of the
integral function on the output signal.
Direct Access Number — F363
Parameter Type —
Numerical
Factory Default —
0.1
Changeable During Run —
Yes
Minimum — 0.01
Maximum — 100.00
PID Deviation Upper Limit
Program
Feedback
Feedback Settings
This parameter determines the maximum amount that the feedback may
increase the output signal.
Direct Access Number — F364
Parameter Type —
Numerical
Factory Default —
50.00
Changeable During Run —
Yes
Minimum — 0.00
Maximum — 50.00
Units — %
PID Deviation Lower Limit
Program
Feedback
Feedback Settings
This parameter determines the maximum amount that the feedback may
decrease the output signal.
Direct Access Number — F365
Parameter Type —
Numerical
Factory Default —
50.00
Changeable During Run —
Yes
Minimum — 0.00
Maximum — 50.00
Units — %
PID Feedback Differential Gain
Program
Feedback
Feedback Settings
This parameter determines the degree that the
Differential
function affects the
output signal. The larger the value entered here, the more pronounced the affect
of the differential function for a given feedback signal level.
Direct Access Number — F366
Parameter Type —
Numerical
Factory Default —
0.00
Changeable During Run —
Yes
Minimum — 0.00
Maximum — 2.55
Содержание GX9
Страница 1: ...GX9 ASD Install Op Manual TOSHIBA GX9 ASD INSTALLATION OPERATION MANUAL DN 66893 001 March 2014 ...
Страница 2: ......
Страница 3: ...Document Number 66893 001 March 2014 GX9 ASD Installation Operation Manual ...
Страница 4: ......
Страница 12: ...iv GX9 ASD Installation and Operation Manual ...
Страница 251: ...GX9 ASD Installation and Operation Manual 239 Figure 36 GX9 ASD 5 0 20 HP Enclosure ...
Страница 252: ...240 GX9 ASD Installation and Operation Manual Figure 37 GX9 ASD 25 75 HP Enclosure ...
Страница 253: ...GX9 ASD Installation and Operation Manual 241 Figure 38 GX9 ASD 100 200 HP Enclosure ...
Страница 254: ...242 GX9 ASD Installation and Operation Manual Figure 39 GX9 ASD 250 400 HP Enclosure ...
Страница 255: ...GX9 ASD Installation and Operation Manual 243 Figure 40 GX9 ASD 500 800 HP Enclosure ...
Страница 256: ...244 GX9 ASD Installation and Operation Manual Figure 41 GX9 ASD 900 1200 HP Enclosure ...
Страница 268: ......
Страница 269: ......