![background image](http://html.mh-extra.com/html/toshiba/grd150/grd150_manual_429868014.webp)
GRD150
14
ENVIRONMENTAL PERFORMANCE
Test Standards
Details
Atmospheric Environment
Temperature IEC60068-2-1/2 Operating
range:
−
10
°
C to
+
55
°
C.
Storage / Transit:
−
25
°
C to
+
70
°
C.
Humidity
IEC60068-2-3
56 days at 40
°
C and 93% relative humidity.
Enclosure Protection
IEC60529
Front: IP51 or IP52 with cover
Rear: IP20
Mechanical Environment
Vibration
IEC60255-21-1
Response - Class 1
Endurance - Class 1
Shock and Bump
IEC60255-21-2
Shock Response Class 1
Shock Withstand Class 1
Bump Class 1
Seismic IEC60255-21-3 Class
1
High Voltage Environment
Dielectric Withstand
IEC60255-5
2kVrms for 1 minute between all terminals and earth.
2kVrms for 1 minute between independent circuits.
1kVrms for 1 minute across normally open contacts.
High Voltage Impulse
IEC60255-5
Three positive and three negative impulses of
5kV(peak), 1.2/50
µ
s, 0.5J between all terminals and
between all terminals and earth.
Electromagnetic Environment
High Frequency
Disturbance /
Damped Oscillatory
Wave
IEC60255-22-1 Class 3,
IEC61000-4-12
1MHz 2.5kV applied to all ports in common mode.
1MHz 1.0kV applied to all ports in differential mode.
Electrostatic
Discharge
IEC60255-22-2 Class 3,
IEC61000-4-2
6kV contact discharge.
8kV air discharge.
Radiated RF
Electromagnetic
Disturbance
IEC60255-22-3 Class 3
(
*
)
,
IEC61000-4-3
Note (
∗
): Class 4 with cover
Field strength 10V/m for frequency sweeps of 80MHz to
1GHz and 1.7GHz to 2.2GHz. Additional spot tests at
80, 160, 450, 900 and 1890MHz.
Fast Transient
Disturbance
IEC60255-22-4,
IEC61000-4-4
4kV, 2.5kHz, 5/50ns applied to all inputs.
Conducted RF
Electromagnetic
Disturbance
IEC60255-22-6,
IEC61000-4-6
10Vrms applied over frequency range 150kHz to
100MHz. Additional spot tests at 27 and 68MHz.
Conducted
Disturbance over freq.
Range 15Hz to
150kHz
IEC61000-4-16 Class 3
Varying voltages applied in common mode as follows:
15Hz to 150Hz: 10V
→
1Vrms (20dB/decade)
150Hz to 1.5kHz: 1Vrms
1.5kHz to 15kHz: 1
→
10Vrms (20dB/decade)
15kHz to 150kHz: 10Vrms
Power Frequency
Disturbance
IEC60255-22-7
300V 50Hz for 10s applied to ports in common mode.
100V 50Hz for 10s applied to ports in differential mode.
Not applicable to AC inputs.
Содержание GRD150