GRD150
12
Phase Undercurrent Protection
Undercurrent 1
st
, 2
nd
threshold:
OFF, 0.10 – 2.00A in 0.01A steps (1A rating)
OFF, 0.5 – 10.0A in 0.1A steps (5A rating)
DTL Delay:
Inst, 0.01 – 300.00s in 0.01s steps
Broken Conductor Protection
Broken conductor threshold (I
2
/I
1
):
OFF, 0.10 – 1.00 in 0.01 steps
DTL delay:
Inst, 0.01 – 300.00s in 0.01s steps
CBF Protection
CBF threshold:
OFF, 0.10 – 2.00A in 0.01A steps (1A rating)
OFF, 0.5 – 10.0A in 0.1A steps (5A rating)
CBF back trip DTL:
Inst, 0.01 – 300.00s in 0.01s steps
CBF Retrip DTL:
Inst, 0.01 – 300.00s in 0.01s steps
Accuracy
IDMTL Overcurrent Pick-up:
Setting value
±
5%
All Other Overcurrent Pick-ups:
Setting value
±
5%
Overcurrent PU/DO ratio:
≥
95%
Undercurrent Pick-up:
Setting value
±
5%
Undercurrent PU/DO ratio:
≤
105%
IDMTL Overvoltage Pick-up:
Setting value
±
2%
All Other Overvoltage Pick-ups:
Setting value
±
2%
Inverse Time Delays:
±
5% or 30ms (1.5 to 30 times setting)
Definite Time Delays:
±
1% (for more than 1s setting) or 10ms
Transient Overreach for instant. elements:
<
−
5% for X/R = 100.
Synchronism Check Function (option)
Synchronism check angle:
5 – 75
°
in 1
°
steps
Frequency difference check:
0.02 – 0.50Hz in 0.01Hz steps
Voltage difference check:
5.0 – 150.0V in 0.1V steps
Voltage dead check:
5.0 – 150.0V in 0.1V steps
Voltage live check:
5.0 – 150.0V in 0.1V steps
Auto-Reclose (option)
ARC Reclaim Time
0.0 – 600.0s in 0.1s steps
Close Pulse Width
0.01 – 10.00s in 0.01s steps
Lock-out Recovery Time
OFF, 0.1 – 600.0s in 0.1s steps
Sequences
1 – 5 Shots to Lock-out, each trip programmable for Inst or
Delayed operation.
Dead Times
(programmable for each shot)
0.01 – 300.00s in 0.01s steps
Metering Function
Current
IL1, IL2, IL3, 3Io. Accuracy
±
0.5% (at rated frequency)
Voltage
V12, V23, V31, 3Vo. Accuracy
±
0.5% (at rated frequency)
Power
P, Q, cos
φ
, Wh, varh. Accuracy
±
1% (at rated frequency)
Frequency Accuracy
±
0.05Hz
Control and Monitoring Function
Control devices
Circuit breaker
×
1,
Disconnector
×
5,
Earthing disconnector switch
×
2
Control input
Interlock setting
Interlock bypass setting
Operate time counter
Breaker travel time
Double command blocking
Control blocking
Содержание GRD150
Страница 1: ......