![Toshiba GRD150 Скачать руководство пользователя страница 15](http://html.mh-extra.com/html/toshiba/grd150/grd150_manual_429868015.webp)
GRD150
15
Test Standards
Details
Surge Immunity
IEC60255-22-5
1.2/50
µ
s surge in common/differential modes:
Auxiliary power supply: 2kV/1kV (peak)
Input/Output: 2kV/1kV (peak)
RS485 port: 1kV (peak)
Conducted and
Radiated Emissions
IEC60255-25
EN55022 Class A
Conducted emissions:
0.15 to 0.50MHz:
<
79dB (peak) or
<
66dB (mean)
0.50 to 30MHz:
<
73dB (peak) or
<
60dB (mean)
Radiated emissions:
30 to 230MHz:
<
30dB
230 to 1000MHz:
<
37dB
Power Frequency
Magnetic Field
IEC61000-4-8 Class 4
Field applied at 50Hz with strengths of:
30A/m continuously,
300A/m for 1 second.
PRPTOCOL CONVERTER G1PR2 (OPTION)
Ratings
Power supply:
110Vdc/100Vac Operative range: 88 - 150Vdc of 110Vdc rated voltage
80 - 120Vac of 100Vac rated voltage
220Vdc/200Vac Operative range: 170 - 300Vdc of 220Vdc rated voltage
200 - 240Vac of 200Vac rated voltage
48Vdc
Operative
range: 38.4 - 72Vdc
Burden:
less than 20W
Communication port
RS232C interface
Connector type
Cable type
RS232C 9-pin D-subminiature connector female
Multi-core (straight)
RS485 interface
Connector
Cable type
Screw terminals (Phoenix Contact, FRONT type)
Twisted pair cable
Optical interface
Operative Range:
Wavelength:
Connector type:
Fibre type:
less than 1.2km with 62.5/125
µ
m GI fibre (3dB/km)
850nm
ST
62.5/125
µ
m glass fibre
IRIG-B
Connector
Screw terminals (Phoenix Contact, FRONT-MSTB type)
Mechanical design
Enclosure Protection
Weight
Installation
IEC60529, IP20 (excluding terminal parts)
5 kg
Flush mounting
Atmospheric Environment
Temperature
Humidity
IEC60068-2-1/2
IEC60068-2-3
Operating range: -10
°
C to +55
°
C.
Storage / Transit: -25
°
C to +70
°
C.
56 days at 40
°
C and 93% relative humidity.
Содержание GRD150