4.HYDRO UNIT
Engineering Data book
41
Heating capacity and input specifications
▼
Outdoor unit
HWS-1103H8-E, HWS-1103H8R-E
Hydro unit
HWS-1403XWH**-E
Rated heating capacity and power input
* Rated heating capacity and power input are the data at rated compressor operating frequency
* Power input does not include water pump power.
* Heating capacity and power input are measured in accordance with EN14511.
Rated condition 1
LWT=35°C
dT=5deg
Capacity
kW
11.2
Power input
kW
2.39
COP
W/W
4.69
Rated water flow rate
/min
32.1
Rated condition 2
LWT=45°C
dT=5deg
Capacity
kW
11.2
Power input
kW
3.19
COP
W/W
3.51
Rated water flow rate
/min
32.1
TO
:
Outdoor temperature (DB°C) RH85%
LWT
:
Leaving water temperature (°C)
dT
:
Delta temperature (deg)
Leaving water temperature - return water temperature