7. HYDRO UNIT INSTALLATION MANUAL
Engineering Data Book
Setting DIP Switches on the Board in Second Remote controller
(option)
• Detach the front cover of the Remote controller.
• Set the DIP switches on the main board
12
1
Used when a hot water cylinder is connected to
system.
OFF = hot water cylinder connected;
ON = hot water cylinder not connected
OFF
2
Used to activate Zone 1 Operation.
OFF = Zone 1 activated;
ON = Zone 1 de-activated
OFF
3
Used to activate Zone 2 Operation.
OFF = Zone 2 de-activated;
ON = Zone activated
OFF
4
Not Used
–
–
–
–
–
13
1
Used to determine type of 3 way diverting valve
used on system.
OFF = 2 SPST type valve;
ON = SPDT type valve
OFF
2
Used to activate external boiler output.
OFF = external boiler output de-activated;
ON = external boiler output activated
OFF
3
Used to activate system auto restart after power
failure.
OFF = auto restart activated;
ON = auto restart de-activated
OFF
4
Not Used
–
–
–
–
–
DIP No.
Description
Default
After
Commissioning
Change 1 Change 2 Change 3
1
Used to when a second remote controller is connected
OFF=Header remote control; ON=Second remote
control
OFF
–
–
–
–
2
Used to determine control target when use second
remote controller
OFF=water temperature;
ON;room temperature
OFF
–
–
–
–
3
Not Used
–
–
–
–
–
4
Not Used
–
–
–
–
–
SW No.
DIP No.
Description
Default
After
Commissioning
Change 1 Change 2 Change 3
Содержание ESTIA HWS-1501CSHM3-E
Страница 3: ...2 1 INTRODUCTION ...
Страница 7: ...6 2 SYSTEM OVERVIEW ...
Страница 11: ...10 3 SYSTEM SPECIFICATION ...
Страница 60: ...59 5 OUTDOOR UNIT ...
Страница 79: ...78 6 HOT WATER CYLINDER ...
Страница 85: ...84 7 HYDRO UNIT INSTALLATION MANUAL ...
Страница 132: ... 131 7 HYDRO UNIT INSTALLATION MANUAL Engineering Data Book MEMO ...
Страница 133: ...132 8 OUTDOOR UNIT INSTALLATION MANUAL ...
Страница 162: ... 161 8 OUTDOOR UNIT INSTALLATION MANUAL Engineering Data book MEMO ...
Страница 163: ...162 9 OWNER S MANUAL ...
Страница 179: ...Air to Water Heat Pump Engineering Data Book Oct 2010 ...