4.HYDRO UNIT
Engineering Data book
39
Cooling capacity and input specifications
▼
Outdoor unit
HWS-1403H-E
Hydro unit
HWS-1403XWH**-E
Rated cooling capacity and power input
* Rated cooling capacity and power input are the data at rated compressor operating frequency
* Power input does not include water pump power.
* Cooling capacity and power input are measured in accordance with EN14511.
Rated condition 1
LWT=7°C
dT=5deg
Capacity
kW
11.0
Power input
kW
4.08
EER
W/W
2.70
Rated water flow rate
/min
31.5
Rated condition 2
LWT=18°C
dT=5deg
Capacity
kW
11.0
Power input
kW
2.65
EER
W/W
4.15
Rated water flow rate
/min
31.5
TO
:
Outdoor temperature (DB°C)
LWT
:
Leaving water temperature (°C)
dT
:
Delta temperature (deg)
Return water temperature - Leaving water temperature