Cooling capacity and power input
* Cooling capacity and power input are the data at rated compressor operating frequency of rated condition 1
* Power input does not include water pump power.
* Cooling capacity and power input are measured in accordance with EN14511.
Capacity (kW)
LWT (°C)
7
10
13
15
18
TO
(°C)
20
10.09
11.06
12.03
12.67
13.63
27
10.40
11.40
12.40
13.06
14.05
30
10.02
10.98
11.95
12.58
13.54
35
9.37
10.27
11.17
11.77
12.66
40
8.66
9.50
10.33
10.88
11.57
43
8.24
9.03
9.82
10.35
10.91
Power input (kW)
LWT (°C)
7
10
13
15
18
TO
(°C)
20
2.04
2.07
2.10
2.12
2.14
27
2.67
2.71
2.75
2.77
2.80
30
2.80
2.84
2.88
2.91
2.94
35
3.00
3.05
3.10
3.12
3.15
40
3.32
3.37
3.42
3.45
3.47
43
3.51
3.56
3.62
3.64
3.66
COP
LWT (°C)
7
10
13
15
18
TO
(°C)
20
4.94
5.34
5.72
5.98
6.37
27
3.89
4.20
4.50
4.71
5.02
30
3.58
3.86
4.14
4.33
4.61
35
3.12
3.37
3.61
3.77
4.02
40
2.61
2.82
3.02
3.16
3.34
43
2.35
2.53
2.72
2.84
2.98
TO
:
Outdoor temperature (DB°C)
LWT
:
Leaving water temperature (°C)
Содержание ESTIA HWS-1501CSHM3-E
Страница 3: ...2 1 INTRODUCTION ...
Страница 7: ...6 2 SYSTEM OVERVIEW ...
Страница 11: ...10 3 SYSTEM SPECIFICATION ...
Страница 60: ...59 5 OUTDOOR UNIT ...
Страница 79: ...78 6 HOT WATER CYLINDER ...
Страница 85: ...84 7 HYDRO UNIT INSTALLATION MANUAL ...
Страница 132: ... 131 7 HYDRO UNIT INSTALLATION MANUAL Engineering Data Book MEMO ...
Страница 133: ...132 8 OUTDOOR UNIT INSTALLATION MANUAL ...
Страница 162: ... 161 8 OUTDOOR UNIT INSTALLATION MANUAL Engineering Data book MEMO ...
Страница 163: ...162 9 OWNER S MANUAL ...
Страница 179: ...Air to Water Heat Pump Engineering Data Book Oct 2010 ...