– 120 –
7. HYDRO UNIT INSTALLATION MANUAL
Engineering Data Book
7
10
Night Setback
Change Setback Temperature
26
–
3~20°C
5
Zone selection 0=Zone 1 & 2;
1= Zone 1 Only
58
–
0~1
1
Start Time (Hour)
–
0E
0~23
22
End Time (Hour)
–
0F
0~23
06
12
Hydro 2 Way
Valve Operation
Control
Cooling 2 Way Valve -
Operation Logic 0=Activated
during cooling; 1=Not
activated during cooling
3C
–
0~1
0
13
Hydro 3 Way
Diverting Valve
Operation Control
3 Way Diverting Valve
Operation Logic 0=Activated
during hot water operation;
1=not activated during hot
water operation
54
–
0~1
0
14
2 Zone Mixing
Valve Drive Time
Specified Drive Time for
Mixing Valve (x10sec)
0C
–
3~24
6
Mixing valve OFF (control time
- mins)
59
–
1~30
4
15
Boiler/Heat Pump
Synchronisation
External Boiler/Heat Pump
Synchronisation
0=Synchronised; 1=Not
synchronised
3E
–
0~1
0
16
Maximum
Operation Time Of
Hot Water Heat
Pump
Maximum Heat Pump
Operation Time In Hot Water
Operation Priority Mode
(minutes)
07
–
1~120
30
17
Cooling Operation
0=Cooloing & Heating
Operation; 1=Heating Only
Operation
02
–
0~1
1
18
Remote Controller
Indication
24h or 12h Time Indication 0=
24h; 1=12h
–
05
0~1
0
19
CDU Night Time
Low Noise
Operation
Low Noise Operation
0=Invalid; 1=Valid
–
09
0~1
0
Start Time (Hour)
–
0A
0~23
22
End Time (Hour)
–
0B
0~23
06
20
Alarm Tone
Tone Switching 0=OFF; 1=ON
–
11
0~1
1
21
E-Stop Switch
Logic
0 = Contacts low > high
system stop. System restart
with remote controller
1 = Contacts high > low
system stop. System restart
with remote controller
2 = Contacts high > low
system stop. Contacts low >
high system restart
3 = Contacts low > high
system stop. Contacts low >
high (second time) system
restart
52
–
0~3
0
0 = Restart hot water and
heating
1 = Restart in the mode when
stopping
2 = Restart hot water
3 = Restart heating
4 = Tempo control 1; without
heater
5 = Tempo control 2; without
HP and heater
61
–
0~5
0
22
Hydro Unit
Capacity Setting
0012 = 80*XWH**E
0017 = 140*XWH**E
Factory set but function code
is needed for PCB
replacement or function code
reset procedure has been
completed.
01
–
0012 or
0017
Depends
on Hydro
Unit
Location & FC
Number
FC Description
Hydro
RC
Range
Default
After
Commissioning
Change
1
Change
2
Содержание ESTIA HWS-1501CSHM3-E
Страница 3: ...2 1 INTRODUCTION ...
Страница 7: ...6 2 SYSTEM OVERVIEW ...
Страница 11: ...10 3 SYSTEM SPECIFICATION ...
Страница 60: ...59 5 OUTDOOR UNIT ...
Страница 79: ...78 6 HOT WATER CYLINDER ...
Страница 85: ...84 7 HYDRO UNIT INSTALLATION MANUAL ...
Страница 132: ... 131 7 HYDRO UNIT INSTALLATION MANUAL Engineering Data Book MEMO ...
Страница 133: ...132 8 OUTDOOR UNIT INSTALLATION MANUAL ...
Страница 162: ... 161 8 OUTDOOR UNIT INSTALLATION MANUAL Engineering Data book MEMO ...
Страница 163: ...162 9 OWNER S MANUAL ...
Страница 179: ...Air to Water Heat Pump Engineering Data Book Oct 2010 ...