26
Voltage Coast Drop Detection Enable : If enable, this second condition on the battery test is activated. On smaller
battery, the rise in current during a boost test might be to small to have a conclusive test. This second test verify the
capacitive effect on the battery line after a boost sequence.
Battery Fail From Engine RPM During Crank : If enable, the Battery Fail alarm will be activated if no RPM is read
after a crank cycle
Charger 1-2 Power Supply Voltage Reference : This is the voltage that is applied by the battery charger in power
supply mode (no battery connected). To measure this voltage, the battery must be disconnected.
Timers Page
Config > Advanced > Timers1-2
Most common timers for fire pump control can be configured here. Note that any timer set to 0 will remove the delay
in the decision process.
Access level 1:
- Engine starting and stopping:
The “Sequential Start Timer” allows a delayed response on an automatic start request.
- Energize to Stop:
This timer set the time in second the fuel solenoide valve will close after a stop.
- Fail When Running Timer: