18
Alarms (Membrane button)
Alarms
Displays the list of currently active and occurred alarms. An alarm is called ACTIVE when its triggering condition is
present. An alarm is called OCCURED when its triggering condition has been active, but is no longer true. Alarms
representing serious concerns are RED. Alarms representing simple warnings are YELLOW. To silence the bell
press the ALARM button or it will silence itself after the expiration of a factory set timer. Pressing on the RESET
button will reset OCCURED alarms only.
The bell test button will activate the alarm bell for 3 seconds.
The table displays system events:
- Date and Time: Date and time stamp of the alarm in the YYYY.MM.DD format
- Message: Alarm message
- State: OCCURED or ACTIVE
- Color Code:
- Red: The event is an alarm
- Yellow: The event is a warning
Complete list of alarms :
Common Alarms:
Engine Trouble: The Engine Trouble common alarm is active when one or more of these conditions are active :
- Engine High Coolant Temperature
- Engine Low Coolant Temperature
- Engine Low Oil Pressure
- Engine Fail to Start
- Engine Overspeed*
- Battery Failure 1-2
Pump Room Trouble: A common alarm activated when the following events occur:
- Fuel Tank Leak
- Low Fuel Level
- High Fuel Level
- AC Failure
- Water Reservoir Low
- Water Reservoir High
- Water Reservoir Empty