24
character and the "CA" button clears the whole text field. Simply click the "OK" button once the value is set. This
type of text field is mostly used to generate a digital text indication for a custom alarm input.
Advanced Configuration Page
Config > Advanced
This page is the portal to all the advanced configuration parameters of the ViZiTouch.
All timers, sensors, factory settings, software update, service dealer and debug pages may be accessed simply by
clicking on the appropriate buttons.
Since two of the analog inputs are using the same physical connector, only one of these can be installed at once.
These analog inputs are shown in the grey box surrounded by a black dotted line. Each time one of these sensors
is installed, the other will turn orange, preventing the dual installation of these sensors.
All buttons are set to security "Level 0" except "Update Program" which is set at "Level 1" security.
Details of the Advanced Configuration Page
Volt-Current Calibration
Config > Advanced > Calibration Voltage-Current
This page is used to calibrate all analog voltages. The actual column shows the actual value calculated by the
ViZiTouch. The “desired” column allows a level 2 user to enter the desired value read from a calibrated external
device (multimeter). For the AC voltage and the 2 DC voltage, the calibration is done by entering the desired value
and pressing on the “COMPUTE” buttons. The DC values must be entered with no batteries connected, to allow the