39
-Enable in Remote: If checked, activation of the lockout input will prevent the Remote start.
-Enable in Flow: If checked, activation of the lockout input will prevent the Flow start.
Interlock is an Output that prevents a second engine from starting.
-Engine Run Required: If enabled, the controller will wait to have Engine Run before putting Interlock active.
-Enable in Manual: If checked, this option will activate the output Interlock on a Manual start.
-Enable in Automatic: If checked, this option will activate the output Interlock on a Automatic start.
-Enable in Remote: If checked, this option will activate the output Interlock on a Remote start.
-Enable in Flow: If checked, this option will activate the output Interlock on a Flow start.
Inputs
Config > Advanced > Inputs
This page is for vizualisation purpose only. It allow the user to verify which signal is mapped on which controller's
input.
I/O Card Info
Config > Advanced > IO Card Info
This page is used to visualize the ViZitouch and the IO Card registers by pressing on the blue arrows on the right of
the screen. Expansion Cards can also be installed via this page.