27
-
Engine Overspeed*: Activates if the specific “Overspeed” input (3) is triggered on the engine connector strip and
the engine is running. This alarm will immediately stop the engine and cannot be reset by using the reset button on
the alarm page. The alarm must be reset on the engine itself and the controller must be turned OFF and ON with
the HOA selector switch to complete the reset procedure for this alarm.
- Battery1-2 Overvoltage: Activates if the voltage of the specific battery is higher than the specified overvoltage set
point.
-
Water Reservoir High: Activates if the optional “Water Reservoir High” contact input is triggered or if the analog
readout of the water level is Enabled and goes higher than the “High Water Level” set point alarm page.
- IO Exp Comm Error: Activates if communication with the Expansion IO board could not be established for 15
seconds.
- Pump on demand: Activates when the pressure is below the cut-in set-point on an automatic pressure actuated
controller.
- Bell Silenced: Activates when a audible alarm has been silenced.
-
Engine Run: Activates when the input “Engine Run“ (2) is active on the engine strip of the IO card.
- Invalid Cut-In: Activates when the Cut-In value is not acceptable. (0 or higher than the Cut-Out).