Silence Duration: Set the time this Alarm will remain silenced.
Annunciate when occurred: Check this box to keep activated any associated relay even when this alarm has
occurred.
Acknowledgeable: Check this box to make the alarm acknowledgeable. If an alarm is ackowledged, the bell will be
silenced and the alarm IO board Output will stop being active. To acknowledge an alarm, go to the alarm list page
and press the blue “Active” status on the right of the alarm. The “Active” status should change to “Acknowledge”.
Timer On: It is the time delay between the triggering of the condition and the activation of the alarm.
Timer Off: It is the time delay between the stopping of the condition and the deactivation of the alarm.
Analog Value Usage: It is used to describe the activation range of the alarm. “Lower Than”, “Higher Than” and
“Between” can be selected. The corresponding value has to be entered.
Text: This field can be used to change the name of the alarm that will be displayed while this alarm is active. Note
that changing the factory set name of an alarm will disable any translation of this alarm to different languages.
Hysteresis: In the “Analogue Value Usage” field, it is possible to chose “Hysteresis Low Setpoint” and “Hysteresis
High Setpoint”. Both Analog Low Value and High Value needs to be selected for this mode to be effective. For the
“Hysteresis Low Setpoint”, the alarm will be trigger if the chosen signal goes below the “Low Setpoint” and will be
reset when the signal rise above the “High Setpoint”. For the “Hysteresis High Setpoint”, the alarm will be trigger if
the chosen signal goes above the “High Setpoint” and will be reset when the signal falls below the “Low Setpoint”.
Chargers and Batteries
Config > Advanced > Chargers and Batteries
This page is used to adjust some features of the batteries and chargers.
Charger 1-2 reference voltage: This is the normal voltage of the chargers in float mode and serves as a reference to
trigger the “charger fail” alarm.
Weak battery 1-
2: Under this voltage, the batteries are considered weak. The alarm “weak battery” is then
activated.
Battery 1-2 overvoltage: Over this voltage, the batteries are considered in overvoltage. The alarm
“battery
overvoltage” is then activated.
Battery missing count before alarm: This is the number of “battery missing” test that needs to be failed before the
“battery failed” alarm is triggered.