26
- Pressure Transducer fault detected: Occurs if the pressure reading is out of its normal range. Additionnally, if an
optional dual pressure sensor is installed, it will be activated if the two pressure transducers show different
readings. Further investigation is advised to determine what caused the different readings. Note that the controller
will always choose the lowest pressure reading to determine the actual system pressure.
- Overpressure: Activates if the analog readout of the discharge pressure goes higher than the overpressure set
point in the alarm page.
-
Underpressure: Activates if the analog readout of the discharge pressure goes lower than the “Under Pressure”
set point in the alarm page.
- Low Suction Pressure: Activates if the analog readout of the suction pressure is Enabled and goes lower than the
low suction pressure set point in the alarm page.
-
Water Reservoir Low: Activates if the “Water Reservoir Low” contact input (IN5) is triggered or if the analog
readout of the water reservoir is Enabled and is lower than the water reservoir low set point in the alarm page.
-
Fuel Tank Leak: Activates if the “Fuel Tank Leak” contact input (IN4) is triggered.
-
Low Fuel Level: Activates if the “Low Fuel Level” contact input (IN1) is triggered or if the analog readout of the fuel
level is Enabled and goes lower than the low fuel level set point alarm.
-
High Fuel Level: Activates if the “High Fuel Level” contact input (IN5) is triggered or if the analog readout of the
fuel level is Enabled and goes higher than the high fuel level set point alarm.
-
Engine Fail When Running: Activates if the “Engine Run” signal is lost while the engine is running. The engine will
try to start the cranking sequence once again if the starting causes are not back to normal.
- Engine Fail to Start: Activates if the engine fail to start after the complete 6 attempts crank sequence. The engine
will turn red.
-
ECM Selector Switch in Alternate Position: Activates if the specific “ECM” (Electronic Control Module) input (301)
is triggered on the engine connector strip.
-
ECM Warning: Activates if the specific “ECM” input (303) is triggered on the engine connector strip.
-
ECM Fault: Activates if the specific “ECM” input (304) is triggered on the engine connector strip.
- FIM: Activates if the specific FIM (Fuel Injection Malfunction) input (302) is triggered on the engine connector strip.
- PLD Low Suction Pressure: Activates if the specific PLD (Pressure Limiting Device) input (305) is triggered on the
engine connector strip.
- High Raw Water Level: Activates if the specific input is (310) triggered on the engine connector strip.
- Low Raw Water Flow: Activates if the specific input (311) is triggered on the engine connector strip.
-
Engine High Temperature: Activates if the specific “High Temp” input (5) is triggered on the engine connector strip
and the engine is running. A 3 hour timer will start when the engine stops, and if the condition is still present, the
alarm will be activated. This alarm will stop the engine only if triggered during a manual run test or a weekly test.
-
Engine Low Temperature: Activates if the specific “Low Temp” input (312) is triggered on the engine connector
strip.
-
Engine Low Oil Pressure: Activates if the specific “Low Oil Pressure” input (4) is triggered on the engine connector
strip and the engine is running. This alarm will stop the engine only if triggered during a manual run test or a weekly
test.