Chapter 7: PC SOFTWARE OFFLINE SETTINGS
9. OPErATION SETTING mODE
7-43
Step 3.
Set the [Evacuation] pattern(s).
3-1.
click on the [Evacuation Pattern] tab.
3-2.
Select "Evacuation" message for EV message.
3-3.
Select the output zone(s) to which the evacuation message is to be broadcast.
The pattern name is displayed in the pattern name list. The pattern name can be changed.
3-4.
Select the control output to be activated during evacuation message broadcast.
Continued on next page