CFP-600L Conventional Fire Alarm Control Panel
- 8 -
9.
General Display and Operation
9.1
Normal
In normal condition the panel should only have a
”Power On” LED lighted up while all other LEDs off.
9.2
Fire
When a Fire is registered by the panel, the Common Fire and Zone Fire LED indicators will light up. All the
fire alarm outputs (Sounder, Fire Alarm and Fire Auxl Outputs )from the panel will activate.
Press “Silenced Alarm” button to silence the sounder outputs and investigate area
or
Press “Reset” button if found to be a false alarm or “Evacuate” button to resound all sounders when a real
fire is detected.
9.3
Fire in Delay Mode
The fire zone indicator will blink quickly and panel buzzer will sound, once the delay is up the fie indicator
will become steady and all sounders and fire outputs will activate.
9.4
Fault
When a Fault is registered by the panel, the Common Fault LED indicator will light up, internal buzzer will
beep and fault relay will de-activate. Fault detail will also be displayed on the panel.
Press
“Mute Buzzer” button to silence the internal buzzer and investigate or rectify the fault. Fault indicator
will switch off automatically once the fault condition is cleared.
Panel Fault
Indicator