CFP-600L Conventional Fire Alarm Control Panel
- 7 -
d)
1 Fire Relay Output:
Output terminals for fire alarm equipment. It provides a voltage free output when
panel detects a fire, it will remain activated until the fire is reset by the panel. Normally Open or Normally
Closed selection by jumping setting and contract rating at 24v 1Amp.
e)
1 Fault Relay Output:
Output terminals for fault monitoring purpose. The output relay is energised
during normal condition and de-energised when in fault condition. Normally Open or Normally Closed
selection by jumping setting and contract rating at 24v 1Amp.
f)
1 Resettable 24v Output:
This 24v, 0.5Amp output will cut off for 5 seconds each time the reset button is
pressed.
g)
1 Aux 24v Output:
Auxiliary 24v 0.5Amp
h)
MAP:
Connection to Main Alarm Panel, this connection is only applicable for Sub Alarm Panel only
i)
CAN:
Network command for Sound, Silence and Rest.
8. Power Supply Unit
30vdc Power Supply Unit
Technical Specifications;
Power:
75W
AC INPUT:
100 ~ 240V / Max 1.5A
AC Freque
ncy: 50 ~ 60Hz
DC output:
30V / 2.3A
+ V ADJ:
Output voltage adjustment pot
CON1 terminals as follows;
1= Neutral, 2= Live, 3= Earth, 4= - 24V, 5= +24V
+V ADJ
C
O
N
1
1
2
3
4
5