TNA CFP-600L Скачать руководство пользователя страница 14

 

 

 CFP-600L Conventional Fire Alarm Control Panel 

- 13 - 

 

12 

Panel cannot 
silence or reset 
when fire 

1)  3 min delay is enabled 
2)  key switch is lock 

1)  Disable 3 minute delay 

13 

Delay mode not 
working 

1)  Zone setup error 
2)  Delay time not set 
3)  Day/Night Mode not enabled 

1)  Set zone to detector 
2)  Set Delay Time 
3)  Enable Day/Night mode 

 

13.  Maintenance 

Fire alarm panel should only be maintained by trained personnel, failure to do so may result damaging the panel 
or even injuries.  

To ensure continuous reliability of the fire alarm system it should be checked and serviced regularly.  It is also 
a good practice to keep a log book at the panel to record all activities. 

The followings are general guides on the interval and scope of works. 

13.1 

Daily Check 

 

Check panel for any fault. 

 

Keep a record for any fault in log book. 

 

Rectify fault immediately.  

 

Take necessary action such as increase surveillance of affect area. 

 

13.2 

Monthly Test 

 

Monthly test check should include all the inspections described in daily check 

 

Simulate fire and fault condition on all zones to ensure system is operational. 

 

Confirm with monitoring station that fire and fault signals have been received. 

 

Check charger voltage and standby battery. 

 

Test power failure condition.  

 

Check panel visual and audible warning with lamp test button. 

 

Check operation of all fire alarm output. 

 

Visually inspect the condition of components, termination and cables. 

 

Ensure panel is clean and tidy. 

 

13.3 

Annual Test 

 

Annual test should in include all the inspections described in monthly test. 

 

The maintenance/servicing personnel should arrange to check the operation of at least 20% of 

the  detectors  in  an  installation  each  year.  The  selection  of  detectors  to be  tested  should  be 

spread over as many zones as possible and should be made in such a way that all detectors 

in an installation should have been checked at least once in 5 years. 

 

Where the heat-sensitive element of thermal detectors or the enclosure of other detectors are 

found to be coated with paint, dust or any material likely to affect the operation of the detectors, 

such material should be cleaned off or if necessary have the detector replaced. 

 

Содержание CFP-600L

Страница 1: ...CFP 600L 4 8 12 16 Zone Conventional Fire Alarm Panel OPERATION MAINTENANCE MANUAL Tanda Technologies Pte Ltd 217 Kallang Bahru 04 02 Singapore 339 347 65 6291 3176 65 6291 3287 info tandatech com sg ...

Страница 2: ...ication 2 Dimension 3 Internal View 5 Main Module Control Board 6 Main Module Termination Board 8 Zone Module 9 Output Module 11 Input Module 13 Power Supply Unit 15 Charger Board 16 Operation and Display 17 Panel Setup 19 Network Connection 21 Testing and Commissioning 22 Troubleshooting 23 Maintenance 24 ...

Страница 3: ...l zone capacity Settings on the main board enable the panel to operate as a Sub Alarm Panel SAP or as a Master Alarm Panel MAP with the latter having the control to Sound Silence and Reset all the panels in a network Other features include simple and straight forward installation and operation procedures key switch protection against unauthorized access to the system zone test mode day night mode ...

Страница 4: ...ltage 30V g Battery Type Sealed lead acid battery h Maximum battery charging Capacity 2 batteries 12v 7Ah i Maximum internal resistance of battery 1Ω j Maximum operating current 2 5A k Ambient temperature 0 40 l Relative humidity 95 no condensing m Max current for each output 0 5A n End of line resister 4 7kΩ For All Zone and Monitored Output Circuits 4 Dimensions CFP 600 8 Zone Fire Alarm Control...

Страница 5: ...ol and Termination Board Main Module Indicator and Control Boards Front 6 1 LED Indicators a POWER ON Green Panel is energised b MAINS FAULT Yellow Incoming supply disrupted c SYSTEM FAULT Yellow CPU or stored data is corrupted d BATTERY FAULT Yellow Battery weak or connection failure ...

Страница 6: ... except for the Mute Buzzer button b EVACUATE To activate all sounder outputs on the mainboard The evacuate indicator lights up when EVACUATE button is pressed and it switches off when the panel is reset or when the sounders are silenced c SILENCE ALARM To silence all sounder outputs on the mainboard The silence alarm indicator lights up when the Silence Alarm button is pressed during fire d MUTE ...

Страница 7: ...onitoring resistor 4 7kOhm must be placed at the end of every circuit Zone current parameter Open circuit 0 2 8mA Normal 2 8 14 4mA Fire 14 4 32 2mA Short circuit 32 2 38 8mA b 2 Monitored Sounder Outputs Output terminals for conventional sounder or alarm bell Output can be off and on manually by the silence alarm and evacuation buttons Voltage Output 24vdc 0 5mA End of line EOL monitoring resisto...

Страница 8: ...n fault condition Normally Open or Normally Closed selection by jumping setting and contract rating at 24v 1Amp f 1 Resettable 24v Output This 24v 0 5Amp output will cut off for 5 seconds each time the reset button is pressed g 1 Aux 24v Output Auxiliary 24v 0 5Amp h MAP Connection to Main Alarm Panel this connection is only applicable for Sub Alarm Panel only i CAN Network command for Sound Silen...

Страница 9: ...f found to be a false alarm or Evacuate button to resound all sounders when a real fire is detected 9 3 Fire in Delay Mode The fire zone indicator will blink quickly and panel buzzer will sound once the delay is up the fie indicator will become steady and all sounders and fire outputs will activate 9 4 Fault When a Fault is registered by the panel the Common Fault LED indicator will light up inter...

Страница 10: ...in test mode will not activate the fire alarm outputs on the panel and modules when the circuit detects a fire however the panel will still register the Fire with the activation of visual and audible warnings to alert the operator Note this feature is only applicable for zone configured as Detector 9 7 One Man Walk Test Set Testing jumper on the main display board to NC for one man walk test opera...

Страница 11: ...e main board is used to set the day night mode delay time and panel address CFP700 SETTING MAIN BOARD SW Settiing Bit Value SW2 MAP bit1 ONE_MAN_TEST MODE bit2 SYSTEM FAULT TEST bit3 0 0 4zones 0 1 8zones 1 0 12zones 1 1 16zones bit4 bit5 no use bit6 bit7 bit8 SW3 Delay Time Setup For Day Night Miode bit1 8 sec bit2 4 Sec bit3 2 Sec bit4 1 Sec Panel Address Setting When Using Repeater Panel bit5 8...

Страница 12: ...ty to ensure panel is working normally Visual and audible warnings Lamp Test Basic Operations Sound Silence Reset Disable No unusual faults Measure each pair of zone and input and output cables Ensure cables are not shorted to Earth Ensure cables are not shorted or open circuit Ensure cables are free from any external voltage Able to read the EOL resistor value 4 7k ohm Connect the cables to the p...

Страница 13: ... 2 Check battery voltage is within 24v Replace battery if necessary 3 Replace fuse 4 Swtich on BT SW 4 System Fault CPU hang or Memory Corrupted 1 Shut down panel and reboot 5 Earth Fault 1 Cables connected to the panel is check to panel earth 1 Remove all cables to the panel individually and identify the cable that is shorted 6 Zone Fault 1 4 7kOhm End of line resistor not connected 2 Detector re...

Страница 14: ...ons described in daily check Simulate fire and fault condition on all zones to ensure system is operational Confirm with monitoring station that fire and fault signals have been received Check charger voltage and standby battery Test power failure condition Check panel visual and audible warning with lamp test button Check operation of all fire alarm output Visually inspect the condition of compon...

Отзывы: