 CFP-600L Conventional Fire Alarm Control Panel 

- 6 - 

 

g)  Refer to page 20 to configure between Detector and MCP zones.  In night mode the panel will operate 

without delay, fire alarm outputs will activate immediately as long a zone is on fire.  Day mode will cancel 
immediately when a second zone is activated or after a duration of 8 hours.    

 

 

7.  Main CPU and Termination Board 

 

 

a) 

4/8/12/16 Fire Alarm Zones:  

Input terminals for conventional smoke and heat detectors, Manual          

Callpoint, Sprinkler Flow Switch and Sub Alarm Panel.  

 

 

Voltage Output 24vdc   

 

End of line (EOL) monitoring resistor (4.7kOhm) must be placed at the end of every circuit. 

 

Zone current parameter :  

Open circuit 

 0 

– 2.8mA 

Normal   

 2.8 

– 14.4mA 

Fire  

 

14.4 -32.2mA 

Short circuit  

32.2 

– 38.8mA 

 

b) 

2 Monitored Sounder Outputs: 

Output terminals for conventional sounder or alarm bell.  Output can be 

off and on manually by the silence alarm and evacuation buttons 

 

Voltage Output:  24vdc 0.5mA 

 

End of line (EOL) monitoring resistor (4.7kOhm) must be placed at the end of every circuit. 

c) 

1 Monitored Fire Alarm Output (Fire Sent): 

Output terminals for fire alarm equipment.   Output will only 

activate upon fire, it will remain activated until the fire is reset by the panel. 

 

Voltage Output:  24vdc 0.5mA 

 

End of line (EOL) monitoring resistor (4.7kOhm) must be placed at the end of every circuit. 

 

 

 

Содержание CFP-600L

Страница 1: ...CFP 600L 4 8 12 16 Zone Conventional Fire Alarm Panel OPERATION MAINTENANCE MANUAL Tanda Technologies Pte Ltd 217 Kallang Bahru 04 02 Singapore 339 347 65 6291 3176 65 6291 3287 info tandatech com sg ...

Страница 2: ...ication 2 Dimension 3 Internal View 5 Main Module Control Board 6 Main Module Termination Board 8 Zone Module 9 Output Module 11 Input Module 13 Power Supply Unit 15 Charger Board 16 Operation and Display 17 Panel Setup 19 Network Connection 21 Testing and Commissioning 22 Troubleshooting 23 Maintenance 24 ...

Страница 3: ...l zone capacity Settings on the main board enable the panel to operate as a Sub Alarm Panel SAP or as a Master Alarm Panel MAP with the latter having the control to Sound Silence and Reset all the panels in a network Other features include simple and straight forward installation and operation procedures key switch protection against unauthorized access to the system zone test mode day night mode ...

Страница 4: ...ltage 30V g Battery Type Sealed lead acid battery h Maximum battery charging Capacity 2 batteries 12v 7Ah i Maximum internal resistance of battery 1Ω j Maximum operating current 2 5A k Ambient temperature 0 40 l Relative humidity 95 no condensing m Max current for each output 0 5A n End of line resister 4 7kΩ For All Zone and Monitored Output Circuits 4 Dimensions CFP 600 8 Zone Fire Alarm Control...

Страница 5: ...ol and Termination Board Main Module Indicator and Control Boards Front 6 1 LED Indicators a POWER ON Green Panel is energised b MAINS FAULT Yellow Incoming supply disrupted c SYSTEM FAULT Yellow CPU or stored data is corrupted d BATTERY FAULT Yellow Battery weak or connection failure ...

Страница 6: ... except for the Mute Buzzer button b EVACUATE To activate all sounder outputs on the mainboard The evacuate indicator lights up when EVACUATE button is pressed and it switches off when the panel is reset or when the sounders are silenced c SILENCE ALARM To silence all sounder outputs on the mainboard The silence alarm indicator lights up when the Silence Alarm button is pressed during fire d MUTE ...

Страница 7: ...onitoring resistor 4 7kOhm must be placed at the end of every circuit Zone current parameter Open circuit 0 2 8mA Normal 2 8 14 4mA Fire 14 4 32 2mA Short circuit 32 2 38 8mA b 2 Monitored Sounder Outputs Output terminals for conventional sounder or alarm bell Output can be off and on manually by the silence alarm and evacuation buttons Voltage Output 24vdc 0 5mA End of line EOL monitoring resisto...

Страница 8: ...n fault condition Normally Open or Normally Closed selection by jumping setting and contract rating at 24v 1Amp f 1 Resettable 24v Output This 24v 0 5Amp output will cut off for 5 seconds each time the reset button is pressed g 1 Aux 24v Output Auxiliary 24v 0 5Amp h MAP Connection to Main Alarm Panel this connection is only applicable for Sub Alarm Panel only i CAN Network command for Sound Silen...

Страница 9: ...f found to be a false alarm or Evacuate button to resound all sounders when a real fire is detected 9 3 Fire in Delay Mode The fire zone indicator will blink quickly and panel buzzer will sound once the delay is up the fie indicator will become steady and all sounders and fire outputs will activate 9 4 Fault When a Fault is registered by the panel the Common Fault LED indicator will light up inter...

Страница 10: ...in test mode will not activate the fire alarm outputs on the panel and modules when the circuit detects a fire however the panel will still register the Fire with the activation of visual and audible warnings to alert the operator Note this feature is only applicable for zone configured as Detector 9 7 One Man Walk Test Set Testing jumper on the main display board to NC for one man walk test opera...

Страница 11: ...e main board is used to set the day night mode delay time and panel address CFP700 SETTING MAIN BOARD SW Settiing Bit Value SW2 MAP bit1 ONE_MAN_TEST MODE bit2 SYSTEM FAULT TEST bit3 0 0 4zones 0 1 8zones 1 0 12zones 1 1 16zones bit4 bit5 no use bit6 bit7 bit8 SW3 Delay Time Setup For Day Night Miode bit1 8 sec bit2 4 Sec bit3 2 Sec bit4 1 Sec Panel Address Setting When Using Repeater Panel bit5 8...

Страница 12: ...ty to ensure panel is working normally Visual and audible warnings Lamp Test Basic Operations Sound Silence Reset Disable No unusual faults Measure each pair of zone and input and output cables Ensure cables are not shorted to Earth Ensure cables are not shorted or open circuit Ensure cables are free from any external voltage Able to read the EOL resistor value 4 7k ohm Connect the cables to the p...

Страница 13: ... 2 Check battery voltage is within 24v Replace battery if necessary 3 Replace fuse 4 Swtich on BT SW 4 System Fault CPU hang or Memory Corrupted 1 Shut down panel and reboot 5 Earth Fault 1 Cables connected to the panel is check to panel earth 1 Remove all cables to the panel individually and identify the cable that is shorted 6 Zone Fault 1 4 7kOhm End of line resistor not connected 2 Detector re...

Страница 14: ...ons described in daily check Simulate fire and fault condition on all zones to ensure system is operational Confirm with monitoring station that fire and fault signals have been received Check charger voltage and standby battery Test power failure condition Check panel visual and audible warning with lamp test button Check operation of all fire alarm output Visually inspect the condition of compon...

Отзывы: