CFP-600L Conventional Fire Alarm Control Panel
- 6 -
g) Refer to page 20 to configure between Detector and MCP zones. In night mode the panel will operate
without delay, fire alarm outputs will activate immediately as long a zone is on fire. Day mode will cancel
immediately when a second zone is activated or after a duration of 8 hours.
7. Main CPU and Termination Board
a)
4/8/12/16 Fire Alarm Zones:
Input terminals for conventional smoke and heat detectors, Manual
Callpoint, Sprinkler Flow Switch and Sub Alarm Panel.
Voltage Output 24vdc
End of line (EOL) monitoring resistor (4.7kOhm) must be placed at the end of every circuit.
Zone current parameter :
Open circuit
0
– 2.8mA
Normal
2.8
– 14.4mA
Fire
14.4 -32.2mA
Short circuit
32.2
– 38.8mA
b)
2 Monitored Sounder Outputs:
Output terminals for conventional sounder or alarm bell. Output can be
off and on manually by the silence alarm and evacuation buttons
Voltage Output: 24vdc 0.5mA
End of line (EOL) monitoring resistor (4.7kOhm) must be placed at the end of every circuit.
c)
1 Monitored Fire Alarm Output (Fire Sent):
Output terminals for fire alarm equipment. Output will only
activate upon fire, it will remain activated until the fire is reset by the panel.
Voltage Output: 24vdc 0.5mA
End of line (EOL) monitoring resistor (4.7kOhm) must be placed at the end of every circuit.