172-65637MA-05  (GP5C  PowerTrap)    8  Jun  2020

 

9

 

Installation 

 

 

Install properly and DO NOT use this product outside the recommended 

operating pressure, temperature and other specification ranges. 

Improper use may result in such hazards as damage to the product or 

malfunctions which may lead to serious accidents. Local regulations 

may restrict the use of this product to below the conditions quoted.

 

CAUTION 

 

 

Use hoisting equipment for heavy objects (weighing approximately 

20 kg (44 lb) or more). Failure to do so may result in back strain or other 

injury if the object should fall.

 

CAUTION 

 

 

Take measures to prevent people from coming into direct contact with 

product outlets. Failure to do so may result in burns or other injury from 

the discharge of fluids.

 

CAUTION 

 

 

 

Do not use excessive force when connecting threaded pipes to the 

product. Over-tightening may cause breakage leading to fluid 

discharge, which may cause burns or other injury.

 

CAUTION 

 

 

 

Use only under conditions in which no water hammer will occur. The 

impact of water hammer may damage the product, leading to fluid 

discharge, which may cause burns or other injury.

 

CAUTION 

 

 

Open System Piping (Steam System Example) 

For non-standard options, please refer to the additional instruction manual(s) provided. 
The following 4 pipes shall be connected to the GP5C: condensate inlet pipe, condensate 
outlet pipe, motive medium supply pipe and exhaust pipe. Refer to 

“Sizing the 

Condensate Receiver Pipe

” for the size of the condensate inlet pipe [Si] (length of Dh). 

 

Q  Pumped Medium 

Sr  Condensate Recovery Line 

St  Steam Trap 

A  Filling Head 

Sm

1

  Motive Medium Supply Pipe 

Vi  Valve on Condensate Inlet Pipe 

Pm  Motive Medium Supply 

Pressure 

Sm

2

  Motive Medium Supply Tube 

Vo  Valve on Condensate Outlet Pipe 

Se  Exhaust Pipe/Tube 

Vm  Valve on Motive Medium Supply Pipe 

Pb  Back Pressure 

Dh  Condensate Receiver   

Ve  Valve on Exhaust Pipe/Tube 

Si  Condensate Inlet Pipe 

Ki  Condensate Inlet Strainer 

Vb  Blowdown Valve 

So  Condensate Outlet Pipe  Km  Motive Medium Strainer 

Pi  Equipment Pressure 

 

 

 

PowerTrap

Pm

Sr

So

Pb

Sm

1

Vm

Km

Vo

St

Se

Ve

Si

Si

Q

Vb

Vi

Ki

A

NOTE:  Pipe the discharge to a 

safe area such as a pit.

Overflow Pipe

Inner diameter should be
at least 8 mm (

5

/

16

in)

Vent Pipe

Condensate Receiver

Dh 

Sm

2

If water hammer due to steam backflow in the condensate recovery 
line is expected, the installation of a check valve vertically and as close 
as possible to the recovery line is recommended.

When the rise in piping is 30 m (100 ft) or further from the PowerTrap, installation of 
a check valve is recommended for the prevention of return water hammer.

Backflow
Water Hammer
Prevention
Check Valve

Backflow
Water Hammer
Prevention
Check Valve

Pi

Содержание PowerTrap GP5C

Страница 1: ...172 65637MA 05 GP5C PowerTrap 8 June 2020 GP5C Copyright 2020 by TLV CO LTD All rights reserved ...

Страница 2: ...stallation 15 Operation and Periodic Inspection 16 Operation 16 Periodic Inspection and Diagnosis 17 Disassembly Reassembly 18 Replacement Parts 19 Recommended Tools List for Disassembly Reassembly 20 1 Before Removing Reattaching 21 2 Removing Reattaching the Body from to the Cover 21 3 Removing Reattaching the Snap action Unit 22 4 Removing Reattaching Each Unit 23 Troubleshooting 24 Determining...

Страница 3: ...nary Also be sure to read this manual carefully before use and follow the instructions to be sure of using the product properly If detailed instructions for special order specifications or options not contained in this manual are required please contact TLV for full details This instruction manual is intended for use with the model listed on the front cover It is necessary not only for installatio...

Страница 4: ...h or serious injury Indicates that there is a possibility of injury or equipment product damage NEVER apply direct heat to the float The float may explode due to increased internal pressure causing accidents leading to serious injury or damage to property and equipment Install properly and DO NOT use this product outside the recommended operating pressure temperature and other specification ranges...

Страница 5: ...dents Be sure to install a vent pipe and an overflow pipe Failure to install an overflow pipe is dangerous as condensate may spurt from the vent pipe and could result in burns and other injuries Pipe the vent pipe and the overflow pipe to a safe place such as a pit After completing all piping work based on the designed piping system make sure that all piping connections are properly and securely t...

Страница 6: ...e model for the open system Check to make sure that the PowerTrap model purchased is suitable for use on the type of system that is being planned for installation Type of System Closed System Open System System Overview Features There is no piping system that opens to the atmosphere and the condensate of 100 C 212 F or more can be recovered No venting of flash steam Small reservoir compared to the...

Страница 7: ...e pressure supplied by the motive medium causes the internal pressure in the unit to become greater than the back pressure The inlet check valve closes and the outlet check valve is pushed open thus discharging the condensate in the unit through the outlet pipe as shown in B below 3 As a result of the condensate in the unit being discharged the water level in the unit drops and the float descends ...

Страница 8: ...ts Local regulations may restrict the use of this product to below the conditions quoted CAUTION Use only under conditions in which no freeze up will occur Freezing may damage the product leading to fluid discharge which may cause burns or other injury CAUTION Refer to the product nameplate for detailed specifications Body Material Cast Iron Body Material Stainless Steel Maximum allowable pressure...

Страница 9: ...g for drainage 15 Seal Set For details please refer to Replacement Parts 1 The maintenance kit should be purchased along with a repair kit or other parts as gaskets might be required 2 A snap action spring is also contained in the snap action unit Motive Medium Inlet Screw 1 2 in Condensate Inlet Flange 1 in Exhaust Outlet Plug Screw 1 4 in Condensate Outlet Screw Flange 1 in Condensate Screwed In...

Страница 10: ...n manual s provided The following 4 pipes shall be connected to the GP5C condensate inlet pipe condensate outlet pipe motive medium supply pipe and exhaust pipe Refer to Sizing the Condensate Receiver Pipe for the size of the condensate inlet pipe Si length of Dh Q Pumped Medium Sr Condensate Recovery Line St Steam Trap A Filling Head Sm1 Motive Medium Supply Pipe Vi Valve on Condensate Inlet Pipe...

Страница 11: ...werTrap as possible and install a union joint for maintenance while allowing sufficient space for maintenance of the strainer Strainers should be angled in the 3 or 9 o clock positions for horizontal installations if installed on a horizontal piping Only use steam compressed air or nitrogen as the motive medium The maximum motive medium supply pressure is 0 5 MPaG 75 psig 5 barg When the motive me...

Страница 12: ...pe thickness should be schedule 40 or less for proper operation Install a condensate inlet strainer Ki 40 mesh or finer on the PowerTrap pumped medium inlet pipe and install a union joint for maintenance The condensate outlet pipe So diameter should be at least 25 mm 1 in During pumping operation the PowerTrap uses the motive medium supply pressure to push out the condensate from the body The GP5C...

Страница 13: ...spurt from the vent pipe and could result in burns and other injuries Pipe the vent pipe and the overflow pipe to a safe place such as a pit Piping size of the overflow pipe should be the same or larger than condensate inlet pipe CAUTION Examples of Overflow Piping for Open Systems Explanations for overflow piping for open systems 1 If flash steam can be discharged from overflow pipe Install overf...

Страница 14: ...f rust becoming clogged and or corrosion since water always present in the loop seal the possibility is greater if the piping diameter is too small generally 25 mm 1 in or smaller Do not install loop seal on the vent pipe Contact TLV if neither 1 nor 2 above can be installed ...

Страница 15: ...1 shown on the next page 3 Determine the overflow pipe diameter Dop refer to the figure below NOTE The overflow pipe diameter should be at least as large as the condensate inlet pipe diameter Dcip refer to the figure below 4 Determine the minimum condensate receiver diameter Dcr refer to the figure below by selecting the largest value among those from i ii and iii based on a condensate receiver le...

Страница 16: ... or less 11 2 100 40 11 2 200 11 2 200 40 11 2 400 11 2 300 50 2 600 2 400 65 21 2 800 21 2 500 80 3 1000 3 NOTE When amount of flash steam and condensate are between two values in the table select the larger value one line below Maintenance Space and Tolerance Angle for Installation Maintenance Space The maintenance space shown in the figure on the left should be provided to enable inspection and...

Страница 17: ...ing or removing the product when it is hot or under pressure may lead to discharge of fluids causing burns other injuries or damage CAUTION Be sure to use only the recommended components when repairing the product and NEVER attempt to modify the product in any way Failure to observe these precautions may result in damage to the product or burns or other injury due to malfunction or the discharge o...

Страница 18: ...be operating cyclically without continuous sound in the motive medium supply pipe or the exhaust pipe during the pumping operation equipment side pressure back pressure c Condensate should not accumulate in the steam using equipment and the temperature of the equipment should not be abnormally low d There should not be any abnormal noise such as water hammer from the pumped medium outlet pipe or t...

Страница 19: ...arge of fluids causing burns other injuries or damage CAUTION Do not use excessive force when connecting threaded pipes to the product Over tightening may cause breakage leading to fluid discharge which may cause burns or other injury CAUTION Use the procedures on the following pages to remove components Use the same procedures in reverse to reassemble Installation inspection maintenance repairs d...

Страница 20: ...e Unit 9 Outlet Check Valve Unit For Body Material FC250 cast iron L 51 5 2 CF8M cast stainless steel L 56 5 21 4 Weight 0 33 kg 0 73 lb Weight 0 38 kg 0 84 lb 139 51 2 194 7 5 8 O ring 4 pcs PTFE Gasket 3 pcs Metal Gasket 1 pc 100 315 16 117 45 8 100 4 84 X Hex Bolt Spring Washer Snap action Unit Coil Spring 19 3 4 11 5 7 16 70 23 4 90 7 3 9 16 60 8 2 3 8 18 5 3 4 Screen Bolt Steel Ball Intake Ex...

Страница 21: ...4 in 22 mm 7 8 in 3 4 6 2 5 4 3 Extension Bar L 150 mm 57 8 in 5 4 Offset Wrench 13 mm 1 2 in 19 mm 3 4 in 22 mm 7 8 in 3 4 6 2 4 5 Adjustable Wrench L 200 300 mm 8 12 in 1 6 6 Needle Nose Pliers 3 7 Hex Key 2 5mm 3 32 in 6 8 Internal Snap Ring Pliers 4 1 N m 10 kg cm2 NOTE If drawings or other special documentation were supplied for the product any torque given there takes precedence over values ...

Страница 22: ...t Body When removing the body lift the float and the float lever slightly to avoid contact with the float Reverse steps in disassembly while referring to the figure below Cover Gasket The gasket may be damaged or destroyed upon disassembly as it is inlaid in the body and may adhere to that groove using a scratch free scraper carefully scrape the gasket from the body Replace with a new gasket if da...

Страница 23: ...e exhaust valve into the bottom of their respective valve seats then continuing to insert all the way up into the valve seat as you reattach the snap action unit Align the snap action unit bolt holes to the bolt holes in the cover Intake Exhaust Valve Remove the intake exhaust valve by rotating it 90 Remove the coil spring Reattach the intake exhaust valve by rotating it 90 Reattach the coil sprin...

Страница 24: ... upwards Tighten to a torque of 10 N m 7 lbf ft Holder Gasket Coil Spring Valve for Outlet Check Valve Take out the holder gasket coil spring and the valve for outlet check valve before removing the outlet check valve Remove the spring holder with a 22 mm 7 8 in socket wrench Be careful not to let the coil spring and the gasket fall Be sure to clean the inside of the outlet check valve Replace wit...

Страница 25: ...ling or removing the product when it is hot or under pressure may lead to discharge of fluids causing burns other injuries or damage CAUTION When the desired performance is not attained with the system in many cases it is due to the following 1 Loose chips from pipe cutting and tapping and or welding scraps or sealant get caught in the intake valve motive medium or check valve and prevent them fro...

Страница 26: ...al to or lower than back pressure Pb Types of Failure Category A G and Corrective Measures Causes 1 4 G 1 2 F 3 1 1 1 1 E 1 4 2 1 2 3 1 3 4 D 1 1 2 3 1 C 1 2 3 1 2 B 2 1 A 1 2 3 1 Is there a continuous flowing sound from the exhaust pipe NO YES NO NO YES NO NO YES NO NO YES Is there a continuous flowing sound from the motive medium supply pipe NO YES NO YES YES NO YES YES NO YES YES Has pumped med...

Страница 27: ...or connect to a separate high pressure line If the back pressure has increased check to see if a steam trap connected to the condensate recovery line is blowing see Steam System Example and check for any valves that have been left closed on the condensate recovery line The motive medium pressure should be equal to or greater than 0 05 MPa 7 psi 0 5 bar higher than the back pressure 2 Insufficient ...

Страница 28: ...the motive medium supply pipe tube and the exhaust pipe tube it is possible that the PowerTrap is faulty Note however that this phenomenon will also occur when the motive medium pressure is equal to or less than the back pressure If the PowerTrap does not operate for long periods of time and the sound of the operating medium can be heard continuously in the motive medium supply pipe tube the Power...

Страница 29: ...aged or defaced nor does it apply in the following cases 1 Malfunctions due to improper installation use handling etc by other than TLV CO LTD authorized service representatives 2 Malfunctions due to dirt scale rust etc 3 Malfunctions due to improper disassembly and reassembly or inadequate inspection and maintenance by other than TLV CO LTD authorized service representatives 4 Malfunctions due to...

Страница 30: ...ictoria 3131 Australia Tel Fax 61 0 3 9873 5610 61 0 3 9873 5010 In East Asia 36 Kaki Bukit Place 02 01 02 Singapore 416214 Tel Fax 65 6747 4600 65 6742 0345 Room 5406 No 103 Cao Bao Road Shanghai China 200233 Tel Fax 86 0 21 6482 8622 86 0 21 6482 8623 No 16 Jalan MJ14 Taman Industri Meranti Jaya 47120 Puchong Selangor Malaysia Tel Fax 60 3 8065 2928 60 3 8065 2923 252 94 K L 17th Floor Muang Tha...

Отзывы: