172-65637MA-05 (GP5C PowerTrap) 8 Jun 2020
15
Vented Receiver Table - 1
Flash Steam
up to ~
kg/hour
Receiver
Diameter
mm (in)
(Length: 1 m)
Vent Line
Diameter
mm (in)
Flash Steam
up to ~
lb/hour
Receiver
Diameter
in
(Length: 3.5 ft)
Vent Line
Diameter
in
25
80
(3)
25
(1)
50
3
1
50
100
(4)
50
(2)
100
4
2
75
125
(5)
50
(2)
150
5
2
100
150
(6)
80
(3)
200
6
3
Vented Receiver Table - 2
Amount of
Condensate
kg/hour
Receiver Diameter
mm (in)
(Length: 1 m)
Amount of
Condensate
lb/hour
Receiver Diameter
in
(Length: 3.5 ft)
50 or less
40
(1
1
/
2
)
100 or less
1
1
/
2
100
40
(1
1
/
2
)
200
1
1
/
2
200
40
(1
1
/
2
)
400
1
1
/
2
300
50
(2)
600
2
400
65
(2
1
/
2
)
800
2
1
/
2
500
80
(3)
1000
3
NOTE: When amount of flash steam and condensate are between two values in the table, select
the larger value (one line below).
Maintenance Space and Tolerance Angle for Installation
Maintenance Space
The maintenance space shown
in the figure on the left should
be provided to enable
inspection and
disassembly/repair of the GP5C
Unit: mm (in)
Tolerance Angle for Installation
The product should be
inclined no more than 3°
front-to-back and left-to-right.
Ensure the product is
horizontal by checking the
machined surface of the
cover top.
100 (4)
100 (4)
1
0
0
(
4
)
Surface to confirm the
product is horizontal