172-65639M-01 (EF200) 13 Apr 2018
64
Pulse simulation
Switch simulation of the pulse output on and off.
• Off
• Fixed value
• Down-counting value
NOTE: If the fixed value option is selected, the Pulse width
parameter defines the pulse width of the pulses output.
Factory setting: Off
Pulse value
When the down-counting value option is selected in the
simulation pulse output parameter, enter the number of pulses
for simulation.
Setting range: 0 to 65535
Factory setting: 0
Switch output
simulation
Switch simulation of switch output on and off.
• Off
• On
Factory setting: Off
Switch status
Select the status of the status output for the simulation.
• Open
• Closed
Factory setting: Open
Simulation device
alarm
Switch the device alarm on and off.
• Off
• On
Factory setting: Off
Diagnostic event
category
Select the category of the diagnostic event.
• Sensor
• Electronics
• Configuration
• Process
Factory setting: Process
Simulation
diagnostic event
Switch simulation of the diagnostic event on and off.
For the simulation, you can choose from the diagnostic events
of the category selected in the Diagnostic event category
parameter.
• Off
• Picklist Diagnostic events (see 10.3)
(depends on the selected category)
Factory setting: Off
8.2.26 Expert
This menu is for use by TLV technical service personnel and does not require
operation during standard flow measurement.
In the event that operation of this menu is required, TLV will explain the
operation procedure.
Consult TLV for more information if required.