172-65639M-01 (EF200) 13 Apr 2018
51
Switch-on delay
NOTE: This function is available when the operating mode is
set to “switch output”.
Define delay for the switch-on of status output.
Factory setting: 0.0 second
Switch-off delay
NOTE: This function is available when the operating mode is
set to “switch output”.
Define delay for the switch-off of status output.
Factory setting: 0.0 second
Failure mode
NOTE: This function is available when the operating mode is
set to “switch output”.
Define output behavior in alarm condition.
• Actual status
• Open
• Closed
Factory setting: Open
Invert output signal
NOTE: This function is available when the operating mode is
set to “switch output”.
Invert the output signal.
• No
• Yes
Factory setting: No
8.2.8 Display: Setup
→
Display
NOTE: See 8.2.17 for advanced settings.
Descriptions of functions: Display
Format display
Select how measured values are shown on the display.
• 1 value, max. size
• 1 ba 1 value
• 2 values
• 1 value large + 2 values
• 4 values
Factory setting: 2 values
Value 1 display
Select the measured value that is shown on the local display.
• Volume flow
• Corrected volume flow
• Mass flow
• Flow velocity
• Temperature
• Calculated saturated steam pressure
• Steam quality (Steam dryness)
• Total mass flow
• Condensate mass flow
• Energy flow
• Heat flow difference
• Reynolds number
• Density
• Pressure
• Specific volume
• Degrees of superheat
• Totalizer 1
• Totalizer 2
• Totalizer 3
• Current output 1
Factory setting: Depends on customer specifications.
0% bargraph value 1 Enter 0% value for bar graph display. (Signed floating-point
number)
Factory setting: 0 m³/h