172-65169MA-08 (MC-COS Multi-control Valve) 28 May 2010
18
Wiring Instructions
Make sure the power supply switch is OFF before carrying out work on
the wiring or inspections involving disassembly.
If such work is carried out with the power on, there is a danger that
equipment may malfunction or electric shock may occur, leading to
injury or other accidents.
CAUTION
Make sure that wiring work requiring a special license is carried out by
qualified personnel.If carried out by unqualified personnel, overheating
or short circuits leading to injury, fires, damage or other accidents may
occur.
CAUTION
Drive Section Terminal Box
When making a connection to the terminal block,
use crimp-style jacks (for M4) with insulation
sleeves.
Recommended Cable Specifications
Cable Specifications
Actuator
Terminal No.
Minimum
Cross Section
mm
2
(in
2
)
Maximum Wire
Gauge No.
(AWG)*
Cable Type
Power Source
1, 2
1.25 (0.002 in
2
) 16
GND
2.00 (0.003 in
2
) 14
Cabtyre Cable
Valve Operation
Signals
3 (shield),
4 (
+
), 5 (
−
)
0.75 (0.001 in
2
) 18
2 conductor
shielded cable
* (American Wire Gauge)
MC-COS
Terminal
Box
Drive Section
Terminal Block
SC-F70/SP-F70
Controller Terminal Block
Shield
Power Supply
100 – 240 V AC
Shielded
Cable
6.3 mm
0.24 in
4.3 mm
0.17 in
6.6 mm
0.26 in
9.0 mm
0.35 in
MAX
MIN