172-65169MA-08 (MC-COS Multi-control Valve) 28 May 2010
35
Malfunctions and Countermeasures
○
:OFF
●
:ON
LE 4, 3, 2, 1
Malfunction Details
Performance of the
actuator when
abnormality occurs
Remedy
○○○○
No malfunction is
detected (All LEDs
are normally OFF)
Continuous operation
○○○●
Operation signal
input error
Continuous operation
Operation input signal is
abnormal.
Make sure that there is no
abnormality with the
controller and the cable for
the operation input signal.
●○○○
Temperature in the
actuator is abnormal
Continuous operation
Make sure that the
temperature around the
drive section is within the
specification range (0 to
50 °C (32 – 122 F°).
○○●●
Motor is overloaded
Motor shuts down, then
keeps rebooting after a
few seconds.
Motor is abnormally
overloaded. Contact TLV.
○●○●
Low motor load
(reducer gear wear,
motor slippage)
Continuous operation
Possibility of abnormal wear
of the gear in the reducer.
Contact TLV.
●○○●
Potentiometer signal
error
Stops when
malfunction occurs
Potentiometer is abnormal.
Contact TLV.
●○●○
Initialization error
Stops when
malfunction occurs
●●○○
E
2
PROM Store Error Stops when
malfunction occurs
If the same phenomenon
occurs after switching the
power OFF and ON, contact
TLV.
○●●●
Motor drive power
voltage is abnormal
Continuous operation Possible abnormality of the
power supply circuit.
Contact TLV.
●○●●
CPU Error
Stops when
malfunction occurs
If the same phenomenon
occurs after switching the
power OFF and ON, contact
TLV.
●●●○
External clock stops
Continuous operation
using internal clock
●●●●
Mode Setting Error
Stops
Possible abnormality of the
internal circuit.
Contact TLV.
○○●○
(spare) Continuous
operation
○●○○
(spare) Continuous
operation
○●●○
(spare) Continuous
operation
●●○●
(spare) Continuous
operation