172-65169MA-08 (MC-COS Multi-control Valve) 28 May 2010
4
Specifications
Install properly and DO NOT use this product outside the recommended
operating pressure, temperature and other specification ranges.
Improper use may result in such hazards as damage to the product or
malfunctions which may lead to serious accidents. Local regulations
may restrict the use of this product to below the conditions quoted.
CAUTION
DO NOT use the trap in excess of the maximum operating pressure
differential; such use could make discharge impossible (blocked).
CAUTION
Use only under conditions in which no freeze-up will occur. Freezing
may damage the product, leading to fluid discharge, which may cause
burns or other injury.
CAUTION
Refer to the product nameplate for detailed specifications.
* Valve No. is displayed for products with options. This item is omitted from the nameplate when there
are no options.
Actuator Specifications
Actuator Model
MC-GA2
Power Source Voltage Free between 100 and 240 V AC (50/60 Hz)
Power Consumption With motor running: 75 VA max.
Insulation Resistance 500 V DC, 100 M
Ω
min. between the power source
terminal and ground terminal
Power Source
Withstand Voltage
Between the power source terminal and ground terminal:
1500 V AC, 1 min. or 1800 V AC, 1 second
Drive System
Positional control by DC brushless motor
Operation Input
(Valve Opening)
4 – 20 mA DC (input impedance 250
Ω
)
Emergency Action
Valve fully closed by an operation signal interruption.
When input power is cutoff: held at position just before
power cutoff
Time Rating
Continuous
Thermal Protection
Built-in overcurrent protection circuit
Time Required to Fully
Open/Close
Fully closed
→
fully open: Approx. 15 seconds
Operation
Manual Operation
Possible with the power OFF
Allowable Ambient Temperature Range 0 to 50 °C (32 to 122 °F)
Allowable Ambient Humidity
10% to 90% RH (without dew)
Allowable altitude
2000m (6600 ft) max.
Vibration Resistance
0.5 G max.
Water Resistance
Rain resistant (equivalent to IP54)
Environment Material
Motor cover: Aluminum
Main mounting plate: cast iron
Primary Pressure Range
Model
Serial Number
Nominal Diameter
Maximum Operating
Temperature
Valve No.*
Secondary Pressure