UCRT INSTALLATION

Do not mount the UCRT junction box on a heat source that exceeds
140oF (60oC).  Examples of improper mounting surfaces include vent
pipe, top of heater casing or any place where radiant or convective heat
would cause the junction box temperature to exceed 140oF. The UCRT
is intended for indoor installation only.

Using the key hole slots on the back of the UCRT junction box as a
template, mark 4 holes on the mounting surface, drill pilot holes if nec-
essary, and secure junction box using provided screws.

The Rooftop Inducer includes a 4’ whip and weatherproof junction box.

The PSA-1 must be mounted with the diaphragm in a vertical position.
See Rooftop Inducer instructions for complete installation details.

ELECTRICAL WIRING 

FIGURE 8050021

UC1

RT SERIES

UC1 or UCRT

PSA-1

2 WIRE +
GROUND

INSTALLER-SUPPLIED

BURNER INTERLOCK

INSTALLER-SUPPLIED

115 VAC CONNECTION

CONNECTION

T

O

RO

O

F

T

O

P

U

N

IT

3 W

I R

E

+

G

R

O

U

N

D

POWER

REQUIREMENTS

EXTERNAL

POWER SWITCHING

CAPACITY

J1 / J2

JUMPER

SAFETY

CIRCUIT

ADD VENTER MOTOR

LOAD PLUS 1/2 AMP

FOR UC1 LOAD

EXTERNAL

CALL TRIGGER

METHODS

J1 / J2

P1 / P2

L / N

3 TO 4

T-BLOCK

T-BLOCK

(RELAY K1)

XL / XN

UC1 CONTROL

M & MTR

(RELAY K2)

T-BLOCK

A / B

24V

1 / 2

115V

1 / 2

OR

OR

USED TO JUMP CALL HOT (24 VAC) OR CALL LINE (115 VAC) FROM TERMINAL 1 TO TERMINAL 3.

CONNECTED TO FAN PROVER.
1 mA @ 5 VDC.  DO NOT SUPPLY POWER HERE.

REMOVE J1-J2 JUMPER IF A DIFFERENT VOLTAGE SOURCE IS PROVIDED TO TERMINAL 3.

120 VAC ±10 %, 50/60 Hz

MOTOR - 1 H.P. MAX. @ 120 VAC, 50/60 Hz

USER-PROVIDED 24 VAC AT TERMINALS 1 & 2.  1 = CALL HOT, 2 = COMMON.  CONTROL
REQUIRES 5 mA @ 24 VAC TO TRIGGER.  MOVE RED VOLTAGE JUMPER TO "24V" LOCATION.

3 mA @ 5 VDC.  MOVE RED VOLTAGE JUMPER TO "DRY" LOCATION.  DO NOT SUPPLY POWER.

USER-PROVIDED CONTACT CLOSURE FROM A TO B.  SIZE CONTACT CLOSURE TO HANDLE

GENERAL PURPOSE - 15A @ 120 VAC, 50/60 Hz 

DURING OPERATION THE CONTROL USES 50 mA MAX @ 120 VAC

MOTOR - 1 H.P. MAX. @ 120 VAC, 50/60 Hz

150 mA MAX @ 120 VAC, 50/60 Hz
CAN ONLY BE CONNECTED TO TJERNLUND-SPECIFIED AUXILIARY DEVICE

CIRCUIT PROTECTION PROVIDED BY INSTALLER

GENERAL PURPOSE - 15A @ 120 VAC, 50/60 Hz

RESISTIVE - 10A @ 28 VDC       PILOT DUTY - 470 VA

USER-PROVIDED 115 VAC AT TERMINALS 1 & 2.  1 = CALL LINE, 2 = NEUTRAL.  CONTROL
REQUIRES 1 mA @ 115 VAC TO TRIGGER.  MOVE RED VOLTAGE JUMPER TO "115V" LOCATION.

D/N 9183006H

ON

PRE-PURGE SETTINGS 

(SEE “PRE-PURGE” ON PAGE 3 PRIOR TO SETTING)

1 2

1 2

1 2

1 2

0 Seconds

5 Seconds

20 Seconds

35 Seconds

P1 & P2 PRE-CYCLE FAN PROVER STATUS CHECK

Pre-Cycle
Prover Status
Check Deactivated 9

The Pre-Cycle Prover Status Check is deactivated from the factory on the UCRT. Natural chimney
draft may be sufficient to close the PSA-1 Fan Prover contacts prior to a call for heat which may
cause nuisance lockouts. The Pre-Cycle Prover Status dip switch #9 should be up or “ON” so that
it is deactivated.

ELECTRICAL SPECIFICATIONS

TYPICAL UCRT, PSA-1 FAN PROVER 

& ROOFTOP INDUCER INSTALLATION

UCRT

ROOFTOP INDUCER
INCLUDES 4’ WHIP
AND WEATHER-
PROOF BOX 

SPEED CONTROL

RED LEAD 

TO INDUCER

6 AMPS MAXIMUM @ 120 VAC 50/60 HZ.

Содержание UCRT

Страница 1: ...ESE INSTRUCTIONS MAY RESULT IN IMPROPER INSTALLATION ADJUST MENT SERVICE OR MAINTENANCE POSSIBLY RESULTING IN FIRE ELECTRI CAL SHOCK CARBON MONOXIDE POISONING EXPLOSION PERSONAL INJURY OR PROPERTY DAM...

Страница 2: ...ight carrier and your distributor immediately and file a concealed damage claim INSTALLATION RESTRICTIONS 1 The Pre Cycle Prover Status Check is deactivated from the factory on the UCRT Natural chimne...

Страница 3: ...ED POWER LED DRY 24 V 115 V APPLIANCE INTERLOCK RELAY INDUCER MOTOR RELAY A B 1 2 3 4 L N J1 J2 XL XN P1 P2 C GND F 1 9 N M MTR J1 J2 CALL JUMPER Used when the call signal is used as the proven return...

Страница 4: ...be cleared NOTE The UC1 board must have its 115 VAC power supply present when any of the 1 8 dip switches are moved back to their original position for the fault code to clear PRE POST PURGE AND PROVE...

Страница 5: ...VOLTAGE SOURCE IS PROVIDED TO TERMINAL 3 120 VAC 10 50 60 Hz MOTOR 1 H P MAX 120 VAC 50 60 Hz USER PROVIDED 24 VAC AT TERMINALS 1 2 1 CALL HOT 2 COMMON CONTROL REQUIRES 5 mA 24 VAC TO TRIGGER MOVE RE...

Страница 6: ...ed in these instructions call Tjernlund s Customer Service Department toll free at 1 800 255 4208 for assistance IMPORTANT If the call for heat interlock signal or 115 VAC power is removed the UC1 boa...

Страница 7: ...heaters To interlock a millivolt water heater and a 24 115 VAC furnace or boiler add the WHKE and MAC1E MILLIVOLT HEATER INSTALLATIONS Each millivolt appliance interlocked with the UC1 must have its o...

Страница 8: ...arity sensitive NOTE If burner safety control goes out on lockout the Inducer will continue to run as long as a call for heat is present UC1 UNIVERSAL CONTROL CONNECTED WITH A 24 VAC ELECTRONIC IGNITI...

Страница 9: ...und wires in UCRT to supply ground Important Installer must supply overload and disconnect protection 5 If not previously completed connect Black White and Red leads from UCRT to like colors in Roofto...

Страница 10: ...ol goes out on lockout the Inducer will continue to run as long as a call for heat is present UC1 UNIVERSAL CONTROL CONNECTED TO A HONEYWELL R7184 SERIES OR EQUIVALENT PRIMARY CONTROL WITH A LINE VOLT...

Страница 11: ...lue and Yellow leads from UCRT to PSA 1 Fan Prover switch Prover Leads are not polarity sensitive NOTE If burner safety control goes out on lockout the Inducer will continue to run as long as a call f...

Страница 12: ...to the ground screw in the Rooftop Inducer whip 4x4 weatherproof box Connect Blue and Yellow leads from UCRT to PSA 1 Fan Prover switch Prover Leads are not polarity sensitive UC1 UNIVERSAL CONTROL C...

Страница 13: ...that a slight positive draft neutral to 0 01 W C or 2 5 Pa is measured at the appliance draft sampling location Flue gases should just start to spill from the draft hood draft diverter or barometric d...

Страница 14: ...original position the fault code will be cleared NOTE The UC1 board must have its 115 VAC power supply present when any of the 1 8 dip switches are moved back to their original position for the fault...

Страница 15: ...4 Red will be reset if the call for heat interlock signal or 115 VAC power is removed If the fan prover makes on start up but breaks for more than 10 seconds during the burner cycle LED 4 will flash...

Страница 16: ...ined return it to your Tjernlund distributor for replacement Please include UCRT date code component was taken from The date code is located on the Electrical Box coverplate If the date code is older...

Отзывы: