TABLE OF CONTENTS

Page (s)

Description and General Information ...............................................................................................................................1
Installation Restrictions and Cautions  ........................................................................................................................1, 2
UC1 Universal Control Board Features  ..........................................................................................................................2
LED Status / Fault Indicators and Fault Retrieval from Memory .................................................................................2, 3
Pre / Post-Purge & Pre-Cycle Prover Status Check Settings ......................................................................................3, 4
UCRT Installation  ...........................................................................................................................................................4
Electrical Wiring

Specifications, Warnings, Sequence of Operation & Internal Schematic .....................................................4, 5
Inducer Ground, Motor and Prover Safety Circuit Connections  .......................................................................6
Multiple and Millivolt Appliance interlocks  ........................................................................................................6
Wiring to Gas Fired Appliance  ......................................................................................................................7-9
Wiring to Oil Fired Equipment  .....................................................................................................................9-11

PSA-1 Fan Proving Switch Adjustment  ........................................................................................................................12
UC1 Operational Check ................................................................................................................................................13
Troubleshooting Electrical Problems ........................................................................................................................13-15
Warranty & Replacement Parts .....................................................................................................................................15

DESCRIPTION

The UCRT combines Tjernlund’s UC1 burner interlock control with an Inducer speed control. It is designed for use 

ONLY

with

Tjernlund RT-Series Rooftop Inducers. Follow these instructions through page 11 for information, options and wiring for the UC1.
Follow PSA-1 proving switch adjustment procedures on page 12 or within the RT-Series Rooftop Inducer Installation Instructions.
The UC1 interlock control can be interlocked with virtually any burner control circuit.  Features include: adjustable pre & post
purge, LED status / diagnostic indicators, 10 second prover switch delay to avoid burner start up and wind induced short cycling.
Interlocks with any 24-115 VAC burner control circuit and also includes “dry” contact actuation option.  After each burner cycle the
UC1 will continue to operate in post-purge mode to allow the Inducer to purge the heater and vent of residual flue gases.  A factory
post-purge time is set at 2 minutes and is adjustable up to 16 minutes, see “Pre / Post Purge and Prover Status Check Dip Switch
Settings” on page 3.

GENERAL INFORMATION

Each UC1 is electrically factory line tested before shipment.

After opening carton, inspect thoroughly for hidden damage.  If any damage is found notify freight carrier and your distributor
immediately and file a concealed damage claim.

INSTALLATION RESTRICTIONS

1. The Pre-Cycle Prover Status Check is deactivated from the factory on the UCRT. Natural chimney draft may be sufficient to 

close the PSA-1 Fan Prover contacts prior to a call for heat which may cause nuisance lockouts. The Pre-Cycle Prover Status 
dip switch #9 should be up or “ON” so that it is deactivated. See page 4 for details.

2.  An Inducer post-purge on the UC1 has been factory set at 2 minutes.  Confirm that dip switch #5 is in the up or "on" position.  

Oil fired equipment requires that the post-purge be long enough to eliminate post cycle nozzle drip odor. A longer post-purge 
may be necessary for longer vent runs or high heat retention, refractory lined combustion chambers. A shorter post-purge may be 
desired for gas installations.  See “Pre / Post Purge Dip Switch Settings” on page 3 for details.

3. The UCRT is intended for indoor installation only.  Do not mount the UCRT on a heat source that exceeds 140oF (60oC).   

Examples of improper mounting surfaces include vent pipe, top of heater casing or any place where radiant or convective heat 
would cause the junction box temperature to exceed 140oF (60oC). 

CAUTIONS

The UC1 must be installed by a qualified installer (an individual properly licensed and/or trained) in accordance with all local 
codes or, in their absence, in accordance with the appropriate National Fire Protection Association #31, #54, #211 and the 
National Electrical Code.  

Failure to install, maintain and/or operate the UC1 in accordance with manufacturer's instructions may result in conditions 
which can produce bodily injury and property damage.

1. The installer must verify that the BTU/hr. input of the appliance does not exceed the recommended input of the any Inducer 

being controlled by the UC1.  Refer to the Rooftop Inducer installation instructions for capacities.

2. Disconnect power supply from the UC1 and heating equipment when making wiring connections and servicing the UC1.

Failure to do so may result in personal injury and/or equipment damage.  LED #6 (RED) should be off with power removed.

Содержание UCRT

Страница 1: ...ESE INSTRUCTIONS MAY RESULT IN IMPROPER INSTALLATION ADJUST MENT SERVICE OR MAINTENANCE POSSIBLY RESULTING IN FIRE ELECTRI CAL SHOCK CARBON MONOXIDE POISONING EXPLOSION PERSONAL INJURY OR PROPERTY DAM...

Страница 2: ...ight carrier and your distributor immediately and file a concealed damage claim INSTALLATION RESTRICTIONS 1 The Pre Cycle Prover Status Check is deactivated from the factory on the UCRT Natural chimne...

Страница 3: ...ED POWER LED DRY 24 V 115 V APPLIANCE INTERLOCK RELAY INDUCER MOTOR RELAY A B 1 2 3 4 L N J1 J2 XL XN P1 P2 C GND F 1 9 N M MTR J1 J2 CALL JUMPER Used when the call signal is used as the proven return...

Страница 4: ...be cleared NOTE The UC1 board must have its 115 VAC power supply present when any of the 1 8 dip switches are moved back to their original position for the fault code to clear PRE POST PURGE AND PROVE...

Страница 5: ...VOLTAGE SOURCE IS PROVIDED TO TERMINAL 3 120 VAC 10 50 60 Hz MOTOR 1 H P MAX 120 VAC 50 60 Hz USER PROVIDED 24 VAC AT TERMINALS 1 2 1 CALL HOT 2 COMMON CONTROL REQUIRES 5 mA 24 VAC TO TRIGGER MOVE RE...

Страница 6: ...ed in these instructions call Tjernlund s Customer Service Department toll free at 1 800 255 4208 for assistance IMPORTANT If the call for heat interlock signal or 115 VAC power is removed the UC1 boa...

Страница 7: ...heaters To interlock a millivolt water heater and a 24 115 VAC furnace or boiler add the WHKE and MAC1E MILLIVOLT HEATER INSTALLATIONS Each millivolt appliance interlocked with the UC1 must have its o...

Страница 8: ...arity sensitive NOTE If burner safety control goes out on lockout the Inducer will continue to run as long as a call for heat is present UC1 UNIVERSAL CONTROL CONNECTED WITH A 24 VAC ELECTRONIC IGNITI...

Страница 9: ...und wires in UCRT to supply ground Important Installer must supply overload and disconnect protection 5 If not previously completed connect Black White and Red leads from UCRT to like colors in Roofto...

Страница 10: ...ol goes out on lockout the Inducer will continue to run as long as a call for heat is present UC1 UNIVERSAL CONTROL CONNECTED TO A HONEYWELL R7184 SERIES OR EQUIVALENT PRIMARY CONTROL WITH A LINE VOLT...

Страница 11: ...lue and Yellow leads from UCRT to PSA 1 Fan Prover switch Prover Leads are not polarity sensitive NOTE If burner safety control goes out on lockout the Inducer will continue to run as long as a call f...

Страница 12: ...to the ground screw in the Rooftop Inducer whip 4x4 weatherproof box Connect Blue and Yellow leads from UCRT to PSA 1 Fan Prover switch Prover Leads are not polarity sensitive UC1 UNIVERSAL CONTROL C...

Страница 13: ...that a slight positive draft neutral to 0 01 W C or 2 5 Pa is measured at the appliance draft sampling location Flue gases should just start to spill from the draft hood draft diverter or barometric d...

Страница 14: ...original position the fault code will be cleared NOTE The UC1 board must have its 115 VAC power supply present when any of the 1 8 dip switches are moved back to their original position for the fault...

Страница 15: ...4 Red will be reset if the call for heat interlock signal or 115 VAC power is removed If the fan prover makes on start up but breaks for more than 10 seconds during the burner cycle LED 4 will flash...

Страница 16: ...ined return it to your Tjernlund distributor for replacement Please include UCRT date code component was taken from The date code is located on the Electrical Box coverplate If the date code is older...

Отзывы: