background image

13

the combustion air opening(s) into the equipment room as outlined in NFPA 31, 54 & 211. Tjernlund’s IN-FORCER

TM

combustion

air intake systems provide a convenient, automated way to supply combustion air to the equipment room. When installing the
Rooftop Inducer it is not necessary to supply any more combustion air than normally required when conventional venting.  

UC1 UNIVERSAL CONTROL OPERATIONAL CHECK

1. Confirm power is supplied to the Control.  LED #6 (RED) should be on.  

2. Activate the UC1 by initiating an appliance call for heat.  LED #1 (AMBER) should be on.

3. The motor relay will close and activate the Inducer motor.  LED #3 (GREEN) should be on.

4. If the safety circuit across P1 & P2 (Inducer Prover) is closed, indicating an approved condition, 

the appliance interlock relay will close making terminal #3 closed to terminal #4 & LED #2  
(BLUE). Appliance burner should fire.

5. Remove power to the UC1 and any interlocked appliances.  The LED #6 (RED) or any LED’s 

should not be on.  Test the safety circuit by removing the Blue or Yellow Lead from PSA-1 Fan 
Proving Switch.  Do not let the opened Lead touch a ground or damage may occur to the control 
when power is Reestablished.  Reestablish power to the UC1 and interlocked appliances and ini-
tiate a  call for heat.  After 60 seconds a Prover Start Up fault should arise with LED #4 flashing 3 times. 

6. Remove appliance call for heat and power to the UC1 and any interlocked appliances.  The LED 

#6 (RED) or any LED’s should not be on.  Reconnect Blue or Yellow Fan Prover lead to PSA-1 
Fan Proving Switch terminal removed from in step 5.

7. Reestablish power to UC1 and interlocked appliances and initiate a call for heat to confirm proper 

operation of UC1 and appliance. 

RESETTING FAULT CODE CREATED BY STEP 5 OF OPERATIONAL CHECK

IMPORTANT:

Prior to accessing the fault code memory, note the settings of the dip switches so that they can be returned to their

original Pre / Post-Purge positions.  When power is supplied to the UC1 use caution when moving dip switches.

The last fault code can be retrieved at any time by setting all dip switches 1-8 to the up, or “on” position.  The last fault code, or
lack there of, will be indicated by counting the number of times LED 4 flashes.  By moving any of the dip switches back to their
original position, the fault code will be cleared.  

NOTE:

The UC1 board must have its 115 VAC power supply present when any of

the (1-8) dip switches are moved back to their original position for the fault code to clear.

TROUBLESHOOTING ELECTRICAL PROBLEMS

The following guide is intended to be used if a problem occurs during the use of the Inducer and UC1.  It may be necessary to
measure voltage during troubleshooting.  

Extreme caution must be exercised to prevent injury.

If you are unable to determine

the defective part with the use of this guide, call your Tjernlund distributor or Tjernlund Products direct at 1-800-255-4208 for fur-
ther assistance.

IMPORTANT:

If the call for heat interlock signal or 115 VAC power is removed, the UC1 board will reset and any fault, if present,

will be stored in memory instead of displayed.  See page 3, “Checking Memory for Last Fault Code”.

LED STATUS & FAULT INDICATORS

LED INDICATOR LIGHTS 

LED #1 (Amber)  Appliance call for heat.
LED #2 (Blue) 

Safety circuit through P1 & P2 (Inducer Fan Prover and/or Limit). Indicates Inducer prover is closed 
during run cycle. Burner circuit is energized with Interlock Relay contact closure from terminal 3 to 4.  

LED #3 (Green)  Power switched to Inducer motor from L to MTR & M.
LED #4 (Red) 

Status / Fault indicator.

LED #5 (Red)

Used as a status indicator.

LED #6 (Red)

115 VAC power supplied to board. 

LED STATUS INDICATORS

LED #4 & #5 (Red) Flashing Alternately

=  Inducer in Pre-purge. (Pre-Purge options 0, 5, 20, 35 seconds)

LED #4 & #5 (Red) Flashing in Unison

=  Inducer in Post-Purge.(Post-Purge options 0, 30 seconds or 1, 2, 4, 8, 16 minutes)

LED #4 Flashes Continuously*

=  Fan Prover opened for more than 10 seconds during burner cycle.

(Inducer will run for 10 minutes, attempting to close Fan Prover)

LED #5 (Red) Flashing Intermittently

=  With no call for heat, flashes 3 seconds on / 3 seconds off if microcontroller is 

working properly.

LED FAULT INDICATORS

Fault conditions are indicated by counting the number of times LED #4 (Red) flashes.

LED #4 Flashes 2 Times

Fan Prover was in electrically closed position prior to Inducer operation.

LED #4 Flashes 3 Times*

Fan Prover does not close within 60 seconds after call for heat.

LED #4 Flashes 4 Times*

Fan Prover opened during cycle and did not close within 10 minutes of Inducer operation.

LED #4 Flashes 5 Times*

Fan Prover opened for more than 10 seconds during burner cycle but closed within 10 minutes.

1        9

LED 1 AMBER
LED 2 BLUE
LED 3 GREEN
LED 4 RED
LED 5 RED

LED 6 RED
POWER LED

ON

Содержание UCRT

Страница 1: ...ESE INSTRUCTIONS MAY RESULT IN IMPROPER INSTALLATION ADJUST MENT SERVICE OR MAINTENANCE POSSIBLY RESULTING IN FIRE ELECTRI CAL SHOCK CARBON MONOXIDE POISONING EXPLOSION PERSONAL INJURY OR PROPERTY DAM...

Страница 2: ...ight carrier and your distributor immediately and file a concealed damage claim INSTALLATION RESTRICTIONS 1 The Pre Cycle Prover Status Check is deactivated from the factory on the UCRT Natural chimne...

Страница 3: ...ED POWER LED DRY 24 V 115 V APPLIANCE INTERLOCK RELAY INDUCER MOTOR RELAY A B 1 2 3 4 L N J1 J2 XL XN P1 P2 C GND F 1 9 N M MTR J1 J2 CALL JUMPER Used when the call signal is used as the proven return...

Страница 4: ...be cleared NOTE The UC1 board must have its 115 VAC power supply present when any of the 1 8 dip switches are moved back to their original position for the fault code to clear PRE POST PURGE AND PROVE...

Страница 5: ...VOLTAGE SOURCE IS PROVIDED TO TERMINAL 3 120 VAC 10 50 60 Hz MOTOR 1 H P MAX 120 VAC 50 60 Hz USER PROVIDED 24 VAC AT TERMINALS 1 2 1 CALL HOT 2 COMMON CONTROL REQUIRES 5 mA 24 VAC TO TRIGGER MOVE RE...

Страница 6: ...ed in these instructions call Tjernlund s Customer Service Department toll free at 1 800 255 4208 for assistance IMPORTANT If the call for heat interlock signal or 115 VAC power is removed the UC1 boa...

Страница 7: ...heaters To interlock a millivolt water heater and a 24 115 VAC furnace or boiler add the WHKE and MAC1E MILLIVOLT HEATER INSTALLATIONS Each millivolt appliance interlocked with the UC1 must have its o...

Страница 8: ...arity sensitive NOTE If burner safety control goes out on lockout the Inducer will continue to run as long as a call for heat is present UC1 UNIVERSAL CONTROL CONNECTED WITH A 24 VAC ELECTRONIC IGNITI...

Страница 9: ...und wires in UCRT to supply ground Important Installer must supply overload and disconnect protection 5 If not previously completed connect Black White and Red leads from UCRT to like colors in Roofto...

Страница 10: ...ol goes out on lockout the Inducer will continue to run as long as a call for heat is present UC1 UNIVERSAL CONTROL CONNECTED TO A HONEYWELL R7184 SERIES OR EQUIVALENT PRIMARY CONTROL WITH A LINE VOLT...

Страница 11: ...lue and Yellow leads from UCRT to PSA 1 Fan Prover switch Prover Leads are not polarity sensitive NOTE If burner safety control goes out on lockout the Inducer will continue to run as long as a call f...

Страница 12: ...to the ground screw in the Rooftop Inducer whip 4x4 weatherproof box Connect Blue and Yellow leads from UCRT to PSA 1 Fan Prover switch Prover Leads are not polarity sensitive UC1 UNIVERSAL CONTROL C...

Страница 13: ...that a slight positive draft neutral to 0 01 W C or 2 5 Pa is measured at the appliance draft sampling location Flue gases should just start to spill from the draft hood draft diverter or barometric d...

Страница 14: ...original position the fault code will be cleared NOTE The UC1 board must have its 115 VAC power supply present when any of the 1 8 dip switches are moved back to their original position for the fault...

Страница 15: ...4 Red will be reset if the call for heat interlock signal or 115 VAC power is removed If the fan prover makes on start up but breaks for more than 10 seconds during the burner cycle LED 4 will flash...

Страница 16: ...ined return it to your Tjernlund distributor for replacement Please include UCRT date code component was taken from The date code is located on the Electrical Box coverplate If the date code is older...