43
Smart valve positioner
TS800/TS805 Series
tissin
COMPENSA
This parameter corrects the error between LCD value and actual valve
opening.
NOTICE
This function should only be used with Linear type products and Rotary
products must be set to 0%.
Range
-50.0~50.0%
Factory setting
TS800L(Linear type)
3.0%
TS800R(Rotary type)
0.0%
ACT NORM
Change the action type of the valve.
Reverse Action
Direct Action
Mode
ACT NORM
Reverse Action
ACT REVE
Direct Action
Factory setting
ACT NORM
OUT NORM
Set the feedback signal from the positioner can be output at the same
percentage as the valve stroke, or the opposite percentage.
Normal
Reverse
Mode
OUT NORM
Normal action
OUT REVE
Reverse action
Factory setting
OUT NORM
HT NORMR
Adjusts the valve opening in the forward reverse or direction of HART
communication signal.
Mode
HT NORMR
Direct action
HT REVER
Reverse action
Factory setting
HT NORMR